Mode – Basler Electric BE1-11g User Manual

Page 164

Advertising
background image

152

9424200994 Rev N

Table 58. Common System and Sensing Transformer Combinations

Phase VT

Connection

Phase

Rotation

Aux VT

Connection

Secondary

Phase Voltage

(Phase-Neutral)

Secondary

Aux Voltage

Angle

Compensation

3-wire

ABC

AB

69.3

120

0

°

3-wire

ABC

BC

69.3

120

240

°

3-wire

ABC

CA

69.3

120

120

°

3-wire

ACB

AB

69.3

120

0

°

3-wire

ACB

BC

69.3

120

120

°

3-wire

ACB

CA

69.3

120

240

°

4-wire

ABC

AN

69.3

69.3

0

°

4-wire

ABC

BN

69.3

69.3

240

°

4-wire

ABC

CN

69.3

69.3

120

°

4-wire

ABC

AB

69.3

120

30

°

4-wire

ABC

BC

69.3

120

270

°

4-wire

ABC

CA

69.3

120

150

°

4-wire

ACB

AN

69.3

69.3

0

°

4-wire

ACB

BN

69.3

69.3

120

°

4-wire

ACB

CN

69.3

69.3

240

°

4-wire

ACB

AB

69.3

120

330

°

4-wire

ACB

BC

69.3

120

90

°

4-wire

ACB

CA

69.3

120

210

°

AB

ABC

AB

69.3

120

0

°

AB

ACB

AB

69.3

120

0

°

BC

ABC

BC

69.3

120

0

°

BC

ACB

BC

69.3

120

0

°

AB

ABC

BC

69.3

120

240

°

AB

ACB

BC

69.3

120

120

°

AB

ABC

AN

69.3

69.3

330

°

AB

ACB

AN

69.3

69.3

30

°

Mode

Two operating modes are available: Phase Lock Loop and Anticipatory. In both modes, the BE1-11g
adjusts the frequency and voltage of the generator to match that of the bus (mains) at the proper relative
phase angle, and then connects the generator to the bus by closing the breaker. Anticipatory mode has
the added capability of compensating for the breaker closing time (the delay between when a breaker
close command is issued and the breaker contacts close). The BE1-11g controls the slip frequency
difference between the generator and the bus, and then calculates the advance angle that is required to
compensate for the breaker closure time.

Synchronization is accomplished using the Raise and Lower logic outputs for the voltage and frequency.
These logic outputs can be set to continuous or proportional. Continuous mode turns the required logic
output on until either it is in the synchronization window or overshoots it. Proportional mode toggles the
contacts based on the respective Pulse Width setting, Pulse Interval setting, and calculated error.

Synchronizer (25A)

BE1-11g