9424200994 Rev N

201

Line Length describes the power line parameters for which distance is to be computed over. The
parameters should be entered in units per line length with line length being the actual length of the power
line. Line length is entered as unit-less quantities and, therefore, can be entered in kilometers or miles.
Therefore, the distance results would be in whatever units the line length represented.

Using the Settings Explorer in BESTCOMSPlus, power line parameters can be entered on the System
Parameters, Power System screen. Settings are provided for Positive-Sequence Impedance, Zero-
Sequence Impedance, and Line Length. Refer to Figure 141.

Figure 141. Power System Screen

Note that both Z1-MAG and Z0-MAG are scaled by 10 times to represent the entire length of the power
line. Since the units are in kilometers, the distance results would also be in kilometers.

Distance calculations are performed post-fault using vector data captured during the actual fault. Pre-fault
current vectors are captured three cycles prior to pickup. Fault voltage and current vectors are captured
two cycles after the trip command is issued. The two-cycle wait time allows line transients to settle to
provide results that are more accurate.

To perform the actual distance calculation, the BE1-11g first must determine the faulted phase. Faults can
be categorized depending on the lines faulted. The various categories are LLL, LL, LLG, or LG where
L = line and G = ground.

To determine the faulted phase, the fault vectors are compensated for load flow using the pre-fault data.
Next, the compensated vectors are run through a series of sequence component comparisons. Once the
faulted phase is determined, the fault data along with the line parameters are applied using the Takagi
algorithm to determine the impedance of the faulted line. The impedance is divided by the impedance per
unit length to determine the distance to fault. This method assumes the line is homogenous and that the
line parameters do not change over the length specified. For a non-homogenous line, the distance would
need to be manually corrected.

The distance-to-fault results are limited to

±300% of the specified line length. This limit prevents

erroneous results from being displayed for non-overcurrent type faults, such as over or undervoltage
faults. A computed value greater than maximum line length is reported as n/a (not applicable).