Inverse time verification, Inverse time reset verification, Definite time verification – Basler Electric BE1-11g User Manual

Page 396

Advertising
background image

384

9424200994 Rev N

Step

Pickup

Setting

Low

Actual

Pickup

High

Low

*

Actual

Dropout

High

*

Pass/Fail

15

2.36

2.31 V/Hz

2.41 V/Hz

2.289 V/Hz

2.336 V/Hz

P / F

* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.

Inverse Time Verification

Time Dial Range = 0.0 to 9.9

Timing Accuracy =

±5% or ±50 ms, whichever is greater

Step

Time

Dial

Setting

Percent of

Nominal V/Hz

Step Voltage

Low

Actual Timing

High

Pass/Fail

3

0.5

110%

132 V

47.5 sec

52.5 sec

P / F

3

0.5

120%

144 V

11.875 sec

13.125 sec

P / F

3

0.5

140%

168 V

2.945 sec

3.255 sec

P / F

4

1.0

110%

132 V

95 sec

105 sec

P / F

4

1.0

120%

144 V

23.75 sec

26.25 sec

P / F

4

1.0

140%

168 V

5.985 sec

6.615 sec

P / F

4

2.0

110%

132 V

190 sec

210 sec

P / F

4

2.0

120%

144 V

47.5 sec

52.5 sec

P / F

4

2.0

140%

168 V

11.875 sec

13.125 sec

P / F

Inverse Time Reset Verification

Time Dial Range = 0.0 to 9.9

Timing Accuracy =

±5% or ±50 ms, whichever is greater

Step

Time Dial Setting

Low

Actual Timing

High

Pass/Fail

3

0.5

5.937 sec

6.562 sec

P / F

4

1.0

11.875 sec

13.125 sec

P / F

4

2.0

23.75 sec

26.25 sec

P / F

Definite Time Verification

Time Dial Range = 0 to 600,000

Timing Accuracy =

±0.5% or ±50 ms, whichever is greater

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

3

500 ms

450 ms

550 ms

P / F

4

1,000 ms

950 ms

1,050 ms

P / F

4

5,000 ms

4,950 ms

5,050 ms

P / F

Overexcitation (24) Test

BE1-11g