2 reference offset adjustment, 2) parameter setting, Analog – Yaskawa Σ-V Series AC Servo Drives Rotational Motor Analog Voltage Reference User Manual

Page 121

Advertising
background image

5.5 Torque Control (Analog Voltage Reference)

5-41

5

Op

er

at

io

n

(2) Parameter Setting

Using Pn400, set the analog voltage level for the torque reference (T-REF) that is necessary to operate the ser-

vomotor at the rated torque.

Note: A torque reference above the rated torque can be applied but it may cause an overload (high load) alarm (A.710) or

overload (low load) alarm (A.720) if excessive torque is output for a long time. Refer to

9.1.2 Troubleshooting of

Alarms

.

5.5.2

Reference Offset Adjustment

In

torque

control, the servomotor may rotate at a very low speed with a voltage reference of 0 V. This occurs

because the internal reference voltage of the SERVOPACK has a slight offset of a few millivolts. It is called
"offset."

If the servomotor rotates at a very low speed, the offset needs to be eliminated with the offset adjustment func-
tion.

Use either automatic adjustment or manual adjustment. Automatic adjustment uses the automatic adjustment
parameter for reference offset (Fn009). Manual adjustment uses the manual adjustment parameter for refer-

ence offset (Fn00B).

Pn400

Torque Reference Input Gain

 

 

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

10 to 100

0.1 V

30

(Rated torque at 3.0 V)

Immediately

Setup

Speed

Position

Torque

Torque reference voltage (V)

(Rated torque)

300

200

100

-300

-200

-100

1 3

10 12

0

-3

-10

-12

Setting range
(1.0 to 10.0 V)

Factory Setting

Output torque (%)

Input voltage range (0 to

±

12 V)

Analog

Output torque

Output torque

Offset

Offset adjustment

Torque
reference
voltage

Torque
reference
voltage

The offset is adjusted in the SERVOPACK.
Offset Adjustment Range:

127 to +127

(Torque Reference:

1905 mV to 1905 mV

Offset Setting Unit: 15.0 mV)

Analog

Advertising