Cnt (pulse counter), Help with the cnt command, Counter report – Lexicon 570 User Manual

Page 33

Advertising
background image

28

Dancer Communications, Inc.

COMMAND>COM S

COMMUNICATIONS SETUP

============== =====

1 = Local RS-232 Baud Rate: 38.4k

2 = Smart Gateway Mode: Disabled

3 = Gateway Echo: Disabled

0 = Previous Menu

Choose a Number>3

Gateway Echo: Disabled

Change Present State? [y/n]> Yes

CNT (Pulse Counter)

The Messenger 570 system allows pulse counting on all eight analog inputs. It uses two commands in data mode,
CNT R, to display all eight counters, and CNT O, to clear individual counters.

The maximum transition rate is 100 state transitions/second (50 Hz signal = 50 counts/second) with no two
transitions occurring within less than 10ms of each other. The signal can be a square, saw-tooth, or sine wave, with
a transition being a change from above three volts and below two volts, and vice versa. Total counts are displayed
as decimals.

„

Help with the CNT command

Type CNT at the command prompt and the Messenger 570 system will return a list of valid counter commands
and related instructions.

COMMAND>CNT

INPUT COUNTER FUNCTIONS

===== ======= =========

CNT R Input Counter Report

CNT O Input Counter Operations

„

Counter Report

Type CNT R at the command prompt to view the count totals for all of the inputs.

COMMAND>CNT R

INPUT COUNTER REPORT

===== ======= ======

Outside Air 1

Input #2 1204

Input #3 1

Input #4 1

Input #5 1

Input #6 1

Input #7 1

Input #8 1