Input operation parameters, Input damping, Deadband – Lexicon 570 User Manual

Page 39

Advertising
background image

34

Dancer Communications, Inc.

COMMAND>INP R

INPUT STATUS REPORT

===== ====== ======

Input #1 OK -94 F

Input #2 OK -78 F

Input #3 OK -89 F

Input #4 OK -93 F

Input #5 OK -93 F

Input #6 OK -93 F

Input #7 OK -93 F

Input #8 OK -93 F

Time: 08/03/96 05:53:21

„

Input Operation Parameters

Type INP O at the command prompt to get a sub-menu parameters (applied globally to all inputs) that affect the
sensitivity and responsiveness of the monitored inputs.

COMMAND>INP O

INPUT OPERATIONS

===== ==========

1 = Input Dampening: Enabled

2 = Input Deadband: 1

3 = Rate of change period: 00:00:10 (hh:mm:ss)

0 = Previous Menu

Input Damping

Input damping causes the Messenger 570 to react slowly to a rapidly changing input. For example, if
temperature were being monitored and the temperature probe was moved from an ice bath to a hot water
bath, a damped input would show a gradual change in temperature every 10 to 20 seconds, rather than an
instantaneous change. This option will eliminate many false alarm situations.

COMMAND>INP O

INPUT OPERATIONS

===== ==========

1 = Input Dampening: Enabled

2 = Input Deadband: 1

3 = Rate of change period: 00:00:10 (hh:mm:ss)

0 = Previous Menu

Choose a Number>1

Input Dampening is Enabled

Change Present State? [y/n]> No

Deadband

When set to a value greater than 1, the Messenger 570 system will not report a change in input value until
the change exceeds the deadband.