COMMAND>INP O

INPUT OPERATIONS

===== ==========

1 = Input Dampening: Enabled

2 = Input Deadband: 1

3 = Rate of change period: 00:00:10 (hh:mm:ss)

0 = Previous Menu

Choose a Number>2

Enter New Deadband in ADC counts> 1

Rate-of-Change Period

The rate of change period is the period of time that a Messenger 570 waits in before taking the samples that
are to be used in the rate of change alarm checks. Note: This time period only applies to the rate of change
set point checks. All other set points are checked and acted upon once every 100 ms.

„

Input Setup Parameters

Type INP S at the command prompt to control the configuration parameters for each input. You will get a list
of all configurable inputs. Select the input you wish to configure and you will get a sub-menu containing
parameters for that input.

COMMAND>INP S

SET/CHECK INPUT SETTINGS

========= ===== ========

1 = Input #1 <Label>

2 = Input #2 <Label>

3 = Input #3 <Label>

4 = Input #4 <Label>

5 = Input #5 <Label>

6 = Input #6 <Label>

7 = Input #7 <Label>

8 = Input #8 <Label>

0 = Previous Menu

Choose a Number>1

Input #1

PRESENT SETTINGS

======= ========

01 = Label <Label>

02 = Sensor Type Temperature (°F)

03 = High Alarm Set Point 260

04 = Low Alarm Set Point -94

05 = Response Time 0 Sec.

06 = Output On Set Point 260

07 = Output Off Set Point -94

08 = Calibration Offset 0

09 = Data Logging Enabled

00 = Previous Menu

Choose a Number>