Su05: IO supply overload [xx.0111.00005]

OH4: Heatsink temp. > shutdown temp. -5°C [xx.0119.00000]

OH1: Heatsink overtemperature [xx.0119.00001]

OH3: OH3: Motor temperature (X21) triggered [xx.0119.00015]

OC5: Ixt overload [xx.0119.00050]

Response (Lenze setting printed in bold)

Setting:

C00598/4

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The supply of the I/Os is overloaded. The total current at

pin 1 of X41 ... X43, X50 is higher than 1 A.

Check connected input sensors.

Do not exceed maximally available total current of 1 A.

Response (Lenze setting printed in bold)

Setting:

C00582

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The heatsink temperature now only differs by 5 °C from

the shutdown temperature of the motor.

Prevent further heating, i.e. reduce motor load or set

controller inhibit so that the heatsink can cool down

again.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The heatsink temperature is higher than the fixed limit

temperature (90 ° C).

Maybe the ambient temperature of the controller is too

high or the fan or its ventilation slots are dirty.

• Check control cabinet temperature.

• Clean filter.

• Clean controller.

• If required, clean or replace the fan.

• Provide for sufficient cooling of the device.

Response (Lenze setting printed in bold)

Setting:

C00585

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The motor temperature monitoring at plug X21 has been

tripped.

Possible causes:

• The motor is overheated so that the thermal contact

integrated into the motor has been switched.

• An open circuit or a loose contact at the connections

mentioned above has occurred.

• Check motor temperature monitoring.

• Provide for sufficient cooling of the motor.

• Check terminals for open circuit or loose contact.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The Ixt overload check has tripped.

Possible causes:

• Wrong dimensioning of the device with regard to its

motor load.

• Load cycles are not complied with.

• Check and, if required, correct dimensioning of the

device and the motor load with regard to technical

data.

• Reduce motor load cycles (observe load cycles

according to documentation).