Ce3: can rpdo3 [xx.0135.00003, Cp04: can rpdo4 [xx.0135.00004, Mci1: module missing/incompatible [xx.0140.00013 – Lenze E84DSxxx User Manual

Page 365: Ps01: no memory module [xx.0144.00001, Ps02: par. set invalid [xx.0144.00002, Warning, Ps01: no, Memory module, Xx.0135.00003, Xx.0135.00004

Advertising
background image

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05

365

9

Diagnostics & error management

9.10

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CE3: CAN RPDO3 [xx.0135.00003]

CP04: CAN RPDO4 [xx.0135.00004]

MCI1: Module missing/incompatible [xx.0140.00013]

PS01: No memory module [xx.0144.00001]

PS02: Par. set invalid [xx.0144.00002]

Response (Lenze setting printed in bold)

Setting:

C00593/3

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: Time monitoring for RPDO3 has been

triggered.

• RPDO3 has not been received within the monitoring

time set in

C00357/3

or was faulty.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate electrical interference (e.g. EMC).

• Adjust monitoring time

C00357/3

or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C00593/4

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: Time monitoring for RPDO4 has been

triggered.

• RPDO4 has not been received within the monitoring

time set in

C00357/4

or was faulty.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate electrical interference (e.g. EMC).

• Adjust monitoring time

C00357/4

or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C01501/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The optional communication module has been removed

or there is a connection problem or incompatibility with

the standard device.

• Check connection between the communication

module and standard device.

• Check if the module is plugged in correctly.

• In case of an incompatibility, either the module or the

software of the standard device is out of date. In this

case, please contact Lenze.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Memory module is either not available or not snapped

into place correctly.

• If a memory module has been provided: Plug the

memory module into the slot of the standard device

intended for this purpose.

• If a memory module has been provided: Check if the

memory module has been plugged-in correctly.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The parameter set saved to the memory module is

invalid because it has not been saved completely.

• This can be due to voltage failure or caused by

removing the memory module while saving the

parameter set.

Ensure voltage supply during the storage process and

that the module remains plugged into the slot.