Chapter 5 Programmable Parameters
Table 50 - Ground Fault Parameters Detail
GF INHIBIT TIME (E3 Plus)
This parameter defines the amount of time
for which ground fault detection is
inhibited during a motor starting sequence.
Parameter Number
35
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-135
Group
Advanced Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
10
GF TRIP DELAY (E3 Plus)
This parameter allows the installer to
program a time duration for which a ground
fault condition must exist at the
programmed level prior to the device
tripping.
Parameter Number
36
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-136
Group
Advanced Setup
Units
Seconds
Minimum Value
0
Maximum Value
25.0
Default Value
0.5
GF TRIP LEVEL (E3 Plus)
This parameter sets the ground fault trip
level.
Parameter Number
37
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-137
Group
Advanced Setup
Units
Amps
Minimum Value
0.02
Maximum Value
5.0
Default Value
2.5
GF WARN LEVEL (E3 Plus)
This parameter sets the ground fault
warning level.
Parameter Number
38
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0xB4-1-1 (E3)
2C
hex
-1-138 (E3 Plus)
Group
Advanced Setup
Units
Amps
Minimum Value
0.02
Maximum Value
5.0
Default Value
2.0
GF TRIP INHIBIT (E3 Plus)
This parameter allows the installer to
inhibit a ground fault trip from occurring
when the ground fault current exceeds the
maximum range of the core balance sensor
(approximately 10 A).
NOTE: This feature is only available in
Series B and later devices.
Parameter Number
89
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
Group
Advanced Setup
Units
--
Minimum Value
0 = Disabled
Maximum Value
1 = Enabled
Default Value
0