Ground fault current reporting, Current range, Frequency range – Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 137: Diagnostic parameters, Current range frequency range
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
137
Monitoring Parameters Chapter 6
Ground Fault Current
Reporting
Current Range
The following chart illustrates the minimum and maximum reporting ground
fault current values for a given ground fault current range.
➊
The E3 Plus Overload Relay will report 0 A if the ground fault current is below 50% of the minimum ground fault
current setting for a given range.
➋
The E3 Plus Overload Relay is capable of reporting values greater than the maximum values shown, but the
accuracy of the value is compromised.
➌
The accuracy specified is only applicable to non-distorted sinusoidal currents.
➍
20…100 mA for resistive loads only. For motor loads, consult your local Rockwell Automation sales office or
Allen-Bradley distributor
.
Frequency Range
The E3 Plus Overload Relay is capable of sensing variable frequency ground fault
currents ranging from 20…250 Hz.
Exception:
Any E3 Plus Overload Relay using an external ground fault sensor is
limited to 50/60 Hz detection.
Diagnostic Parameters
The E3 Overload relay provides a number of motor diagnostic parameters to
assist maintenance personnel with information to minimize unplanned down
time. The relay also provides a number of preventative maintenance diagnostics
to maximize the life of an electric motor.
Table 3: Ground Fault Current Reporting Summary
Ground Fault
Current Range
Minimum
Reporting
Current ➊➌
Maximum
Reporting
Current ➋➌
E3 Plus Cat. No. /Series
20…100 mA➍
10 mA
180 mA
193/592-EC3 and -EC5 — Series C
and later
100…500 mA
50 mA
900 mA
193/592-EC3 and -EC5 — Series C
and later
200 mA…1.0 A
100 mA
1.80 A
193/592-EC3 and -EC5 — Series C
and later
1.0…5.0 A
500 mA
9.00 A
193/592-EC2 and -EC5 — Series A
and later