Three-pole terminal blocks, Terminal lug kits – Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual

Page 27

Advertising
background image

Rockwell Automation Publication 193-UM002I-EN-P - December 2011

27

Installation & Wiring Chapter 2

Three-Pole Terminal Blocks

Table 3 - Three-Pole Terminal Blocks

Terminal Lug Kits

Table 4 - Terminal Lug Kits

Control, DeviceNet, & Voltage Input Module Terminals

Table 5 - Wire Size & Torque Specification

Cat. No. 100-DTB1890 (A) 6…1/0 AWG, 16…50 mm

2

(B) 6 AWG…250 MCM, 16…120 mm

2

90…110 lb.-in., 10…12 Nm

100-DTB420

(2) 4 AWG…600 MCM, 25…240 mm

2

180…220 lb.-in., 20…25 Nm

Cat. No. 100-DL 110 Lug

6…2/0 AWG, 16…70 mm

2

90…110 lb.-in., 10…12 Nm

Terminal

13/32 in, 10 mm
150 lb.-in., 17 Nm

180 Lug

6 AWG…250 MCM, 16…120 mm

2

90…110 lb.-in., 10…12 Nm

Terminal

1/2 in., 13 mm
275 lb.-in., 16 Nm

420 Lug

2 AWG…350 MCM
375 lb.-in., 42 Nm

Terminal

11/16 in., 17 mm
140 lb.-in., 16 Nm

630 Lug

2/0 AWG…500 MCM, 70…240 mm

2

400 lb.-in., 45 N

Terminal

3/4 in, 19 mm

600 lb.-in., 68 Nm

860 Lug

2/0 AWG…500 MCM, 70…240 mm

2

400 lb.-in., 45 Nm

Terminal

3/4 in, 19 mm
600 lb.-in., 68 Nm

Wire Type

Conductor Torque All Cat. No. Types

Stranded/Solid [AWG]

Single

24...12 AWG

Multiple
(stranded only)

24...16 AWG
5 lb-in

Advertising