Three-pole terminal blocks, Terminal lug kits – Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual
Page 27
Rockwell Automation Publication 193-UM002I-EN-P - December 2011
27
Installation & Wiring Chapter 2
Three-Pole Terminal Blocks
Table 3 - Three-Pole Terminal Blocks
Terminal Lug Kits
Table 4 - Terminal Lug Kits
Control, DeviceNet, & Voltage Input Module Terminals
Table 5 - Wire Size & Torque Specification
Cat. No. 100-DTB1890 (A) 6…1/0 AWG, 16…50 mm
2
(B) 6 AWG…250 MCM, 16…120 mm
2
90…110 lb.-in., 10…12 Nm
100-DTB420
(2) 4 AWG…600 MCM, 25…240 mm
2
180…220 lb.-in., 20…25 Nm
Cat. No. 100-DL 110 Lug
6…2/0 AWG, 16…70 mm
2
90…110 lb.-in., 10…12 Nm
Terminal
13/32 in, 10 mm
150 lb.-in., 17 Nm
180 Lug
6 AWG…250 MCM, 16…120 mm
2
90…110 lb.-in., 10…12 Nm
Terminal
1/2 in., 13 mm
275 lb.-in., 16 Nm
420 Lug
2 AWG…350 MCM
375 lb.-in., 42 Nm
Terminal
11/16 in., 17 mm
140 lb.-in., 16 Nm
630 Lug
2/0 AWG…500 MCM, 70…240 mm
2
400 lb.-in., 45 N
Terminal
3/4 in, 19 mm
600 lb.-in., 68 Nm
860 Lug
2/0 AWG…500 MCM, 70…240 mm
2
400 lb.-in., 45 Nm
Terminal
3/4 in, 19 mm
600 lb.-in., 68 Nm
Wire Type
Conductor Torque All Cat. No. Types
Stranded/Solid [AWG]
Single
24...12 AWG
Multiple
(stranded only)
24...16 AWG
5 lb-in