Rockwell Automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Plus Solid-State Overload Relay User Manual User Manual

Page 141

Advertising
background image

Rockwell Automation Publication 193-UM002I-EN-P - December 2011

141

Monitoring Parameters Chapter 6

➊ Series C and later

TRIP STATUS

This parameter provides trip
identification.

1 = Trip
0 = No Trip

Parameter Number

14

Access Rule

Get

Data Type

WORD

Object Mapping

0x29-1-114

Group

Monitor

Units

Minimum Value

Maximum Value

Default Value

None

Bits

Function:

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

X

Test Trip

X

Overload

X

Phase Loss

X

Ground Fault (E3 Plus)

X

Stall

X

Jam

X

Underload

X

PTC (E3 Plus)

X

Current Imbalance

X

Comm Fault

X

Comm Idle

X

Nonvolatile Memory Fault

X

Hardware Fault

X

Remote Trip

X

Blocked Start/Start Inhibit ➊