Programmable Parameters Chapter 5
Table 51 - Start Parameters Detail — Series C & Later
GF SENSING RANGE
(E3 Plus, Series C and later)
This parameter selects one of the
Ground Fault Sensing Ranges:
20…100 mA ➊
100…500 mA
200 mA…1.0 A
1.0…5.0 A
Parameter Number
106
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2Chex-1-181
Group
Advanced Setup
Units
0 = 20…100 mA
1 = 100…500 mA
2 = 200 mA…1.0 A
3 = 1.0…5.0 A
Minimum Value
0
Maximum Value
3
Default Value
3
GF WARN DELAY
(E3 Plus, Series C and later)
This parameter allows the installer to
program a time duration for which a ground
fault condition must exist at the
programmed level prior to the device
providing a warning.
Parameter Number
105
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2Chex-1-180
Group
Advanced Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
0
GF FILTER ENABLE
(FRN 5.0 and higher)
This parameter allows the installer to filter
ground fault currents from current based
protection features including Thermal
Overload, Jam, Stall, Under Load, and
Current Imbalance.
Parameter Number
131
Access Rule
Get/Set
Data Type
BOOL
Object Mapping
0Fhex-83-01
Group
Advanced Setup
Units
—
Minimum Value
0 = Disable
Maximum Value
1 = Enable
Default Value
0
➊
For use with resistive loads only. For motor loads, consult factory.
STARTS/HOUR
This parameter allows the installer to limit
the number of starts per hour.
Parameter Number
99
Access Rule
Get/Set
Data Type
USINT
Object Mapping
29hex-1-104
Group
Advanced Setup
Units
—
Minimum Value
0
Maximum Value
120
Default Value
2
STARTS INTERVAL
This parameter allows the installer to limit
the time between starts.
Parameter Number
100
Access Rule
Get/Set
Data Type
UINT
Object Mapping
29hex-1-105
Group
Advanced Setup
Units
Seconds
Minimum Value
0
Maximum Value
3600
Default Value
600