Programmable Parameters Chapter 5

Table 51 - Start Parameters Detail — Series C & Later

GF SENSING RANGE
(E3 Plus, Series C and later)

This parameter selects one of the

Ground Fault Sensing Ranges:
20…100 mA ➊

100…500 mA

200 mA…1.0 A

1.0…5.0 A

Parameter Number

106

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2Chex-1-181

Group

Advanced Setup

Units

0 = 20…100 mA

1 = 100…500 mA

2 = 200 mA…1.0 A

3 = 1.0…5.0 A

Minimum Value

0

Maximum Value

3

Default Value

3

GF WARN DELAY
(E3 Plus, Series C and later)

This parameter allows the installer to

program a time duration for which a ground

fault condition must exist at the

programmed level prior to the device

providing a warning.

Parameter Number

105

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2Chex-1-180

Group

Advanced Setup

Units

Seconds

Minimum Value

0

Maximum Value

250

Default Value

0

GF FILTER ENABLE
(FRN 5.0 and higher)

This parameter allows the installer to filter

ground fault currents from current based

protection features including Thermal

Overload, Jam, Stall, Under Load, and

Current Imbalance.

Parameter Number

131

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0Fhex-83-01

Group

Advanced Setup

Units

Minimum Value

0 = Disable

Maximum Value

1 = Enable

Default Value

0

For use with resistive loads only. For motor loads, consult factory.

STARTS/HOUR

This parameter allows the installer to limit

the number of starts per hour.

Parameter Number

99

Access Rule

Get/Set

Data Type

USINT

Object Mapping

29hex-1-104

Group

Advanced Setup

Units

Minimum Value

0

Maximum Value

120

Default Value

2

STARTS INTERVAL

This parameter allows the installer to limit

the time between starts.

Parameter Number

100

Access Rule

Get/Set

Data Type

UINT

Object Mapping

29hex-1-105

Group

Advanced Setup

Units

Seconds

Minimum Value

0

Maximum Value

3600

Default Value

600