Power Parameters Chapter 8
UPFLG Warn Level
This parameter sets the under power
factor lagging warning level.
Parameter Number
276
Access Rule
Get/Set
Data Type
SINT
Object Mapping
0Fhex-114-01
Group
Power Setup
Units
%
Minimum Value
-100
Maximum Value
0
Default Value
-95
OPFLG Inhibit Time
This parameter defines the amount of
time for which an over power factor
lagging detection is inhibited during a
motor starting sequence.
Parameter Number
277
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-115-01
Group
Power Setup
Units
Seconds
Minimum Value
0
Maximum Value
250
Default Value
10
OPFLG Trip Delay
This parameter allows the installer to
program a time duration for which an
over power factor lagging condition
must exist prior to the device tripping.
Parameter Number
278
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0Fhex-116-01
Group
Power Setup
Units
Seconds
Minimum Value
0.1
Maximum Value
25.0
Default Value
1.0
OPFLG Trip Level
This parameter sets the over power
factor lagging trip level.
Parameter Number
279
Access Rule
Get/Set
Data Type
SINT
Object Mapping
0Fhex-117-01
Group
Power Setup
Units
%
Minimum Value
-100
Maximum Value
0
Default Value
-95
OPFLG Warn Level
This parameter sets the over power
factor lagging warning level.
Parameter Number
280
Access Rule
Get/Set
Data Type
SINT
Object Mapping
0Fhex-118-01
Group
Power Setup
Units
%
Minimum Value
-100
Maximum Value
0
Default Value
-90