Power Parameters Chapter 8

UPFLG Warn Level

This parameter sets the under power
factor lagging warning level.

Parameter Number

276

Access Rule

Get/Set

Data Type

SINT

Object Mapping

0Fhex-114-01

Group

Power Setup

Units

%

Minimum Value

-100

Maximum Value

0

Default Value

-95

OPFLG Inhibit Time

This parameter defines the amount of
time for which an over power factor
lagging detection is inhibited during a
motor starting sequence.

Parameter Number

277

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-115-01

Group

Power Setup

Units

Seconds

Minimum Value

0

Maximum Value

250

Default Value

10

OPFLG Trip Delay

This parameter allows the installer to
program a time duration for which an
over power factor lagging condition
must exist prior to the device tripping.

Parameter Number

278

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0Fhex-116-01

Group

Power Setup

Units

Seconds

Minimum Value

0.1

Maximum Value

25.0

Default Value

1.0

OPFLG Trip Level

This parameter sets the over power
factor lagging trip level.

Parameter Number

279

Access Rule

Get/Set

Data Type

SINT

Object Mapping

0Fhex-117-01

Group

Power Setup

Units

%

Minimum Value

-100

Maximum Value

0

Default Value

-95

OPFLG Warn Level

This parameter sets the over power
factor lagging warning level.

Parameter Number

280

Access Rule

Get/Set

Data Type

SINT

Object Mapping

0Fhex-118-01

Group

Power Setup

Units

%

Minimum Value

-100

Maximum Value

0

Default Value

-90