Rockwell Automation Publication 193-UM002I-EN-P - December 2011

39

Installation & Wiring Chapter 2

Control Wire Requirements

• The maximum length of the shielded cable is 100 feet (30.48 meters).
• All control terminals are for copper wire only in sizes #12…24 AWG.
• Ring lug termination is required for the ground sensor terminals of 193-

CBCT2 and larger.

• The sensor fastener torque is 26…30 lb-in.
• The 193-CBCT1 wires should be twisted before termination by applying

one twist per inch (per 25.4 millimeters).

Table 17 - Control Wire Specifications

Approximate Dimensions

Approximate dimensions are shown in millimeters (inches). Dimensions are not
intended to be used for manufacturing purposes.

IMPORTANT The shield of the twisted pair cable must be connected to earth ground

at the ground fault sensor with no connection made at the E3 Plus
Overload Relay.

Cat. No.

193-

Max.

Current

[A]

Hz

Turns

Ratio

Sensor

Window

I.D.

Max.

Recommended

Cable Size @ 600V

Cat. No.

100-C09 IEC

Contactor

NEMA

Contactor

Size

CBCT1

45

50/60 1000:1 19.1 mm

(.75 in.)

#8 AWG
(10 mm

2

)

…-C37

00…2

CBCT2

90

#2 AWG
(350 mm

2

)

…-C85

00…3

CBCT3

180

#250 MCM
(120 mm

2

)

…-D180

00…4

CBCT4

420

$350 MCM
(185 mm

2

)

…-D240

00…5

For a three-phase system with one cable per phase.

For a three-phase system with two cables per phase.