Table 1-1, Earth types, 2 definition of earth types – Innotech Device Network Cabling User Manual

Page 13: 3 earth points, 2 definition of earth types 1-3 earth points

Advertising
background image

Innotech Device Network Cabling Installation Instructions

© Mass Electronics Pty Ltd 2007

Chapter 1 – Common Requirements

Page 13

1-2 Definition of Earth Types

There are three types of earth referred to in this document:

• Bonded, hard or clean

• Soft

• Floating

These definitions are listed below in relation to the Innotech networks.

Type

Description

Bonded,

Hard or

Clean

A bonded, hard or clean earth is defined as a low impedance earth point with little

or no chance of conducted noise either already present or likely to be created when

bonded to a circuit. For Innotech’s reference we also explicitly mean there is no

potential difference to true earth.

Soft

A soft earth is where there is a path to earth via a circuit. This provides a tie to earth so

potential differences are minimised. This path has higher impedance than a bonded

earth. This does force strong earth currents, i.e. leakage currents from large AC motors,

to remain on the proper heavy gauge earth wires, while leaving the soft earth paths

unaffected. So whilst having multiple earth connections we have not created any

effective earth loops.

Soft earth is often used in 24 V supplied devices. The ‘tie to earth’ is in fact a ‘tie to 0 V’

because there is no dedicated earth terminal available. It is therefore expected that

the 0 V is earthed near the supply transformer.

Floating

Floating simply means that there is no path to an Earth point at all provided by the

device, not even a soft earth path. A floating device has no earth.

Table 1-1: 

Earth Types

1-3 Earth Points

It is imperative that the screen is earthed at one point only and this is defined as any point along a

network that is the best earth point along its length. Where ‘best’ earth point, is the point with least

amount of earth potential fluctuations. i.e. A controller in the basement of a high rise building is

closest to a good earth point than a controller in the plant room on top of the roof.

While there are internal jumpers on some devices to link the ‘S’ terminal internally to earth, there are

variants in hardware types and revisions, simply connect a bonded earth as shown externally. This

will suit all installations, regardless of age. If a repeater is installed each side of the repeater is to be

treated as a separate standalone network and each must have an earth connected.

When there is more than one connection point to earth the screen becomes a conductor and no longer performs

correctly. Care should be taken to ensure only one bonded earth point is ever connected on a primary network.

Refer to Chapter

2-6

for details on use of a Repeater in a primary network.

NOTE

Advertising