Table 6-1, Factory settings for rs486 end of line termination, 1 factory settings – Innotech Device Network Cabling User Manual
Page 44
© Mass Electronics Pty Ltd 2007
Innotech Device Network Cabling Installation Instructions
Page 44
Edition 3.0 dated 05.12.2013
O - Fitted open C - Fitted Closed O/NA - Open with no adjustment available
Part Number
Part Summary
EOL
REM
EOL
Subnet
EOL
Primary Remarks
MAX1 Series
MAXIM I Controller,
Standalone
--
--
--
MAX2 Series
MAXIM II Controller, Primary
Network
--
--
O/NA
No headers
fitted
MAX3 Series
MAXIM III Controller, Primary
Network
--
--
O/NA
No headers
fitted
MAX1010
MAXIM 1010 Controller,
Primary Network
--
--
O/NA
No headers
fitted
MM01
MiniMAX Controller, Primary
Network
--
O/NA
O/NA
GENII V5 DDC
Series
Direct Digital Controller,
Primary Network
C
--
O
MPCIILN
Mid Points Controller, REM
Jumper
C
--
O
VM01
VAVMax Controller, Sub
System Network
--
O
O
Open is
labelled as
‘NODE’
UM01
MicroMAX Controller, Sub
System Network
--
O
O
Open is
labelled as
‘NODE’
MM02
MiniMAX Controller, Sub
System Network
--
O
--
GENII MPI Series Modem Printer Interface
--
--
O
Headers Global
/ NET are
fitted without
jumpers
CONVUSB
Converter, USB – RS485
--
O/NA
O/NA
CONV232
Converter, RS232 – RS485
--
O/NA
O/NA
CONVE
Converter, Ethernet – RS485
--
O/NA
O/NA
GENII VIEWPORT Human Machine Interface
Genesis, RS485
--
--
O
No Jumper
fitted
MP01
Human Machine Interface
Maxim, RS485
--
--
O
No Jumper
fitted
IG01
Sub System Gateway
--
O
O/NA
IG02
Innotech Dynalite Gateway
--
--
O/NA
Header and
Jumper are not
fitted
IG03
BACnet Gateway
--
--
O/NA
MS/TP jumper
should be
open, however
specific BACnet
instructions
take
precedence.
Table 6-1:
Factory Settings for RS486 End of Line Termination
6-1 Factory Settings
The tables in this section list the Factory Settings for RS485 End of Line Termination.