Innotech Device Network Cabling Installation Instructions

Page 44

Edition 3.0 dated 05.12.2013

O - Fitted open C - Fitted Closed O/NA - Open with no adjustment available

Part Number

Part Summary

EOL

REM

EOL

Subnet

EOL

Primary Remarks

MAX1 Series

MAXIM I Controller,

Standalone

--

--

--

MAX2 Series

MAXIM II Controller, Primary

Network

--

--

O/NA

No headers

fitted

MAX3 Series

MAXIM III Controller, Primary

Network

--

--

O/NA

No headers

fitted

MAX1010

MAXIM 1010 Controller,

Primary Network

--

--

O/NA

No headers

fitted

MM01

MiniMAX Controller, Primary

Network

--

O/NA

O/NA

GENII V5 DDC

Series

Direct Digital Controller,

Primary Network

C

--

O

MPCIILN

Mid Points Controller, REM

Jumper

C

--

O

VM01

VAVMax Controller, Sub

System Network

--

O

O

Open is

labelled as

‘NODE’

UM01

MicroMAX Controller, Sub

System Network

--

O

O

Open is

labelled as

‘NODE’

MM02

MiniMAX Controller, Sub

System Network

--

O

--

GENII MPI Series Modem Printer Interface

--

--

O

Headers Global

/ NET are

fitted without

jumpers

CONVUSB

Converter, USB – RS485

--

O/NA

O/NA

CONV232

Converter, RS232 – RS485

--

O/NA

O/NA

CONVE

Converter, Ethernet – RS485

--

O/NA

O/NA

GENII VIEWPORT Human Machine Interface

Genesis, RS485

--

--

O

No Jumper

fitted

MP01

Human Machine Interface

Maxim, RS485

--

--

O

No Jumper

fitted

IG01

Sub System Gateway

--

O

O/NA

IG02

Innotech Dynalite Gateway

--

--

O/NA

Header and

Jumper are not

fitted

IG03

BACnet Gateway

--

--

O/NA

MS/TP jumper

should be

open, however

specific BACnet

instructions

take

precedence.

Table 6-1: 

Factory Settings for RS486 End of Line Termination

6-1 Factory Settings

The tables in this section list the Factory Settings for RS485 End of Line Termination.