Innotech Device Network Cabling Installation Instructions

Edition 3.0 dated 05.12.2013

Page 30

The only device on a REM network without an earth terminal is the IR11 repeater. It must have the 0 V

of its power supply earthed.

Figure 3-1:  REM Network

REM Device

REM Device

REM Device

3-1.1 Soft Earth

All REM devices have a soft earth and as such the Earth must be connected to the terminal ‘E’. This

provides the required path to earth. It is not sufficient to have the 0V earthed on the 24V powered

devices as these are separated.

3-1.2 End of Line Termination (EOL)

All REM’s have EOL jumpers and these must be fitted correctly. See the figures below.

There are many variations to network layouts the following four examples provide a guide to correct

jumper application.

EXAMPLE 1:

This example shows a GENIIELD controller with a straight forward network of REM’s.

Both ends must have the EOL jumpers fitted.

NOTE

Figure 3-2:  Simple REM Network