Figure 3-1, Figure 3-2, Rem network – Innotech Device Network Cabling User Manual
Page 30: Simple rem network, 1.1 soft earth, 1.2 end of line termination (eol), 1.1 soft earth 3-1.2 end of line termination (eol), Rem network simple rem network, Figure 3-1: figure 3-2
© Mass Electronics Pty Ltd 2007
Innotech Device Network Cabling Installation Instructions
Edition 3.0 dated 05.12.2013
Page 30
The only device on a REM network without an earth terminal is the IR11 repeater. It must have the 0 V
of its power supply earthed.
Figure 3-1: REM Network
REM Device
REM Device
REM Device
3-1.1 Soft Earth
All REM devices have a soft earth and as such the Earth must be connected to the terminal ‘E’. This
provides the required path to earth. It is not sufficient to have the 0V earthed on the 24V powered
devices as these are separated.
3-1.2 End of Line Termination (EOL)
All REM’s have EOL jumpers and these must be fitted correctly. See the figures below.
There are many variations to network layouts the following four examples provide a guide to correct
jumper application.
EXAMPLE 1:
This example shows a GENIIELD controller with a straight forward network of REM’s.
Both ends must have the EOL jumpers fitted.
NOTE
Figure 3-2: Simple REM Network