Table 2-1, Primary network digital controllers and devices, Primary network devices – Innotech Device Network Cabling User Manual

Page 16

Advertising
background image

© Mass Electronics Pty Ltd 2007

Innotech Device Network Cabling Installation Instructions

Edition 3.0 dated 05.12.2013

Page 16

Primary Network Devices

There are twenty-three devices that connect directly to the primary Innotech network. These are

listed in table 1 below:

Part

Number

Comms

Terminals

Comms Isolation Screen Type

Description

GENIIxLD

G+

S N+

G-

N-

Fully isolated

Soft Earth to Earth

power terminal 3

Genesis Version 5

Hardware

MPCIILN

G+

S N+

G-

N-

Fully isolated

Soft Earth to Earth

power terminal 3

MPC Version 6

Hardware

GENESIS II V4

G+

S N+

G-

N-

Optional
Full Isolation Card

Tie Terminal

Genesis Version 4

Hardware (obsolete)

GENII MPC

G+

S N+

G-

N-

Fully isolated

Soft Earth to Earth

power terminal 3

MPC Version 4

Hardware

GENESIS II V3

N+

S

N-

G+

S

G-

Optional
Full Isolation Card

Tie Terminal

Genesis Version 3

Hardware (obsolete)

MAXIM 1010

G+

S N+

G-

N-

Robust
High protection

Soft Earth to power

supply 0V terminal

Maxim 1010

MAX3xLx

G+

S N+

G-

N-

Robust
High protection

Soft Earth to power

supply 0V terminal

Maxim Series 3

Hardware

MAX2Lx

G+

S N+

G-

N-

Robust
High protection

Tie Terminal

Maxim Series 2

Hardware

MM01

G+

S N+

G-

N-

Robust
High protection

Soft Earth to power

supply 0V terminal

Mini Maxim Controller

GENII

VIEWPORT

S1

- S2

+

Fully isolated

Soft Earth to power

supply 0V terminal

Viewport Network

Display

MP01

S1

- S2

+

Fully isolated

Soft Earth to Earth

power terminal 3

MiniPort Maxim

Network Display

Table 2-1: 

Primary Network Digital Controllers and Devices

Advertising