Innotech Device Network Cabling User Manual
Page 45
Page 45
Innotech Device Network Cabling Installation Instructions
© Mass Electronics Pty Ltd 2007
Chapter 6 – Factory Settings for RS485 EOL Termination
O - Fitted open C - Fitted Closed O/NA - Open with no adjustment available
Part Number
Part Summary
EOL
REM
EOL
Subnet
EOL
Primary Remarks
IWS01
innSIGHT Supervisor Web
Server
--
--
O/NA
ICS01
Innotech Control Station, Set
Point
--
--
O/NA
Header and
Jumper are not
fitted
ICS02
Innotech Control Station, Set
Point & Fan
--
--
O/NA
Header and
Jumper are not
fitted
IR11
Innotech Repeater, Single
Channel
C
C
--
2 Jumpers
IR12
Innotech Repeater, Dual
Channel
--
--
O
4 Jumpers
GENII RMI
Remote Module Interface
C
--
--
GENII IDI REM
Opto Isolated Digital Input
Module
O
--
--
GENII DO REM
Relay Output Module
O
--
--
GENII DI REM
Dry Contact Digital Input
Module
O
--
--
GENII AO REM
Analogue Output Module
O
--
--
GENII AI REM
Analogue Input Module
O
--
--
GENII PI REM
Pulse Input Module
O
--
--
GENII MP405
REM
Multipoint Remote Expansion
Module
O
--
--
GENII MP414
REM
Multipoint Remote Expansion
Module
O
--
--
GENII MP423
REM
Multipoint Remote Expansion
Module
O
--
--
GENII MP432
REM
Multipoint Remote Expansion
Module
O
--
--
GENII CS REM
Control Station Remote
Expansion Module
O
--
--
GENII CSAH REM Control Station After Hours
Remote Expansion Module
O
--
--
GENII CSFCAH
REM
Control Station With 3 Speed
Fan Remote Expansion
Module
O
--
--
GENII MZS REM
Multi Zone Station Remote
Expansion Module
O
--
--
GENII MZSAH
REM
Multi Zone Station After Hours
Remote Expansion Module
O
--
--
GENII WMI
Wireless Module Interface
O
--
--
Table 6-1 Continued