Innotech Device Network Cabling User Manual
Page 17
Innotech Device Network Cabling Installation Instructions
© Mass Electronics Pty Ltd 2007
Chapter 2 – Primary Networks
Page 17
Part
Number
Comms
Terminals
Comms Isolation Screen Type
Description
GENII RPTR
G+
S N+
G-
N-
Fully isolated
Soft Earth to Earth
power terminal 3
Repeater 9600 baud
(obsolete)
IR12
G+
S N+
G-
N-
Fully isolated
Soft Earth to power
supply 0V terminal
Repeater dual channel
(auto detect dual
baud)
GENII MPI
G+
S N+
G-
N-
Optional
Fully Isolated
Tie Terminal
Modem Printer
Interface
CONV 232
S1
- S2
+
Fully isolated
Floating Earth
RS232 to RS485
converter
CONV E
S1
- S2
+
Fully isolated
Floating Earth
Ethernet to RS485
converter
CONV USB
S1
- S2
+
Fully isolated
Floating Earth
USB to RS485 converter
ICS01
S1
- S2
+
Fully isolated
Soft Earth to Earth
power terminal 3
Control Station type 1
ICS02
S1
- S2
+
Fully isolated
Soft Earth to Earth
power terminal 3
Control Station type 2
IG01
G+
S N+
G-
N-
Robust
High protection
Soft Earth to power
supply 0V terminal
Sub System Gateway
IG02
S1
- S2
+
Fully isolated
Soft Earth to power
supply 0V terminal
Dynalight Gateway
IG03
PC
+
S N+
PC
-
N
-
Robust
High protection
Soft Earth to power
supply 0V terminal
BACnet Gateway
IWS01
PC
+
S N+
PC
-
N
-
Robust
High protection
Soft Earth to power
supply 0V terminal
innSIGHT Supervisor
Web Server
Table 2-1 Continued