Safety engineering

Device modules
SM301 safety module

1

l

22

EDS94AYAE EN 7.0

Terminal assignment

}

Danger!

Danger to life through improper installation
Improper installation of the safety engineering systems can cause
anuncontrolled starting action of the drives.
Possible consequences:

ƒ

Death or severe injuries

Protective measures:
Total cable length between X82 and its connected components (e.g. sensors,
devices, ...) > 3 m:

ƒ

Up to HW version 1A, a shielded laying system must be used for the cable
between X82 and its connected components:
– The shield must at least cover the shield connection at the installation

backplane.

– The shield should also cover the connected component if possible.

ƒ

From HW version 1A onwards, unshielded wiring is permissible.

Total cable length between X82 and its connected components (e.g. sensors,
devices, ...) < 3 m:

ƒ

Unshielded wiring is permissible.

X82.1

Labelling

Description

This part of the terminal strip is not assigned.

GO

GND SD−Out1

O1B

Safe monitor SD−Out1, channel B

O1A

Safe monitor SD−Out1, channel A

This part of the terminal strip is not assigned.

X82.2

Labelling

Description

GND external supply

+

+24 V external supply via a safely separated power supply unit (SELV/PELV)

GIR

This part of the terminal strip is reserved.

RI1

GO

GND 24O

24O

+24 V external supply for the safe monitor SD−Out1 (SELV/PELV)

AIE

Error acknowledgement input ("Acknowledge In Error")

CLA

Clock output for passive sensors, channel A (Clock A)

CLB

Clock output for passive sensors, channel B (Clock B)