Safety engineering, Codes – Lenze E94AYAE SM301 User Manual
Page 46
Safety engineering
Device modules
Safe speed measurement and position detection
l
46
EDS94AYAE EN 7.0
Codes
Parameter:
Name:
Data type:
Index:
C15400
Motor encoder system
UNSIGNED_8
9175
d
= 23D7
h
Selection of the encoder system connected
Selection list
(Lenze setting printed in bold)
Information
0 No encoder system
1 Sin/cos encoder
"Sin/cos encoder" is used instead of the entries
"sine/cosine encoder" and "absolute value encoder
(Hiperface)" of code C00422 of the 9400 standard
device.
2 Resolver
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer
C15401
Motor encoder status
UNSIGNED_8
9174
d
= 23D6
h
Status of the encoder evaluation
Selection list
(read only)
Information
0 Valid
Encoder data is valid
1 Fault
Encoder data is invalid
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer
C15402
Actual speed value n_safe
INTEGER_16
9173
d
= 23D5
h
Display of the current speed calculated from the safety module
Display area
(min. value | unit | max. value)
Information
-16000
rpm
16000 With invalid encoder data (C15401 = 1) 32767 is
displayed.
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer
C15405
Internal actual speed value
INTEGER_16
9170
d
= 23D2
h
Internal actual speed values of SM301.
Display area
(min. value | unit | max. value)
Information
−16000
rpm
16000
(As of SM301 V1.4)
With invalid encoder data (C15401 = 1) 32767 is
displayed.
Subcodes
Information
C15405/1
−
Internal actual speed value nSM detected from motor
position.
C15405/2
−
Internal actual speed value nGG detected from position
data of the standard device.
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer
C15409
Motor mounting direction
UNSIGNED_8
9166
d
= 23CE
h
Setting of the motor mounting direction.
Selection list
(Lenze setting bold)
Information
0 Motor rotating clockwise
(From SM301 V1.4)
1 Motor rotating counter−clockwise
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer
C15410
Response time of encoder monitoring
UNSIGNED_8
9165
d
= 23CD
h
Max. internal time after which encoder errors lead to a system response
Selection list
Information
0 12 ms
(As of SM301 V1.2)
(From SM301 V1.4: Resolver is sole encoder
W
50 or 100 ms)
10 50 ms
20 100 ms
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer