Safety engineering, Device modules safe inputs, Explanations – Lenze E94AYAE SM301 User Manual
Page 32
Safety engineering
Device modules
Safe inputs
l
32
EDS94AYAE EN 7.0
Specification
Sensor type
passive
active
Discrepancy time
parameterisable 0 ... 30000 ms (increment: 2 ms)
Input delay
parameterisable 0 ... 100 ms (increment: 2 ms)
Input filter time for test pulses
fixed 2 ms
Repetition rate of the test pulses
is determined by the clock outputs
CLA and CLB
> 50 ms
Error response
Sensor input is assessed as OFF state.
Acknowledgement via safety bus or AIE input
Tab. 1−2
Specification of sensor connections
Explanations
ƒ
Discrepancy time
Maximum time in which both channels of a safe input may have non−equivalent states
without the safety engineering causing an error response.
ƒ
Input delay
Time between the recognition of the signal change and the effective evaluation of an
input signal. As a result, multiple and short signal changes due to contact bounce of the
components are not taken into account.
ƒ
Input filter time
Time in which the interference pulses and test pulses are not detected by e.g. active
sensors that are switched on.
The input delay time and the time of the input filters influence the response time. More
information can be found in the "Response times" chapter (
¶ 107).
Codes
Parameter:
Name:
Data type:
Index:
C15033
SD-In discrepancy time
UNSIGNED_16
9542
d
= 2546
h
Maximum time in which both channels of a safe input may have non−equivalent states without the safety
engineering causing an error response.
Setting range
(min. value | unit | max. value)
Information
0
MS
30000 Lenze: 10, increment: 2 ms
Subcodes
Information
C15033/1
SD-In1 discrepancy time
C15033/2
SD-In2 discrepancy time
C15033/3
SD-In3 discrepancy time
C15033/4
SD-In4 discrepancy time
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer