Humidity (hum) control method – Liebert CHALLENGER 3000 User Manual

Page 18

Advertising
background image

Operation with Advanced Microprocessor Controls

10

Enable Alarms—Each individual alarm can be selected to be ENABLED (annunciated audibly, visu-

ally, and communicated to a Site Products System) or DISABLED (ignored).
Enable Common Alarm—Each individual alarm can be selected to energize or to not energize the

common alarm relay. If the energize common alarm function is set to YES, the relay is energized

immediately as the alarm is annunciated and de-energized when the alarm condition goes away (only

after the alarm has been recognized). If the function is set to NO, the alarm has no effect on the com-

mon alarm relay regardless of whether the alarm is ENABLED or DISABLED.
Set Custom Alarms—The custom alarm messages can be from a list of standard alarm messages or

you can write your own message.

They can be in any location(s) 1 through 4. The text for custom alarms can be changed at any time by

selecting “SET CUSTOM ALARMS.” To change the text for a custom alarm, select “SELECT

ALARM.” Then, select the alarm you would like to change, 1 through 4. Using the UP/DOWN arrows

will step through the list of five standard alarm messages (see list below) and the two custom alarms.

Press ENTER to make your selection. To modify the two custom alarm messages, go back one screen

and select “CHANGE CUSTOM TXT 1” (or 2). Text can be up to 20 characters in length and can be

any of the following characters (or a blank space):

ABCDEFGHIJKLMNOPQRSTUVWXYZ#%*-0123456789.

Standard Custom Alarm Messages

• WATER UNDER FLOOR
• SMOKE DETECTED
• STANDBY GC PUMP ON
• LOSS OF WATER FLOW
• STANDBY UNIT ON

For more information concerning alarms, see 5.0 - Alarm Descriptions.

Humidity (HUM) Control Method

The user may select between relative (direct) and absolute (predictive) humidity control. If relative is

selected, the RH control is taken directly from the RH sensor. If absolute is selected, the RH control is

automatically adjusted as the return air temperature deviates from the desired temperature setpoint.

This results in a predictive humidity control. The display will indicate % RH for both methods of con-

trol, but the adjusted humidity reading will be displayed if absolute is selected. With absolute humid-

ity control, the humidity control is automatically adjusted approximately 2% RH for each degree

difference between the return air temperature and the temperature setpoint.
With relative humidity control, unnecessary dehumidification can result when overcooling occurs dur-

ing a dehumidification cycle. This is because a higher than normal RH reading is caused by overcool-

ing the room (about 2% RH for each degree of overcooling). This extends the dehumidification cycle.

Later, when the dehumidification ends and the temperature rises to the setpoint, the RH reading

falls. The final RH reading will then be lower than actually desired. If the overcooling was significant

enough, the RH could be low enough to activate the humidifier.
If absolute humidity control is selected, over-dehumidification is avoided. When overcooling occurs,

causing an increase in the RH reading, the humidity control program “predicts” what the RH will be

when the dehumidification cycle ends and temperature returns to the setpoint. This allows the dehu-

midification cycle to end at the proper time. The predictive humidity control can reduce energy con-

sumption by minimizing compressor and reheat operation, and eliminating unnecessary humidifier

operation.

NOTE
A maximum of two of the alarm messages can be your own message.

NOTE
The two custom alarm messages will be shown with what was previously programmed in them

and can be changed.

Advertising