Operation with Advanced Microprocessor with Graphics Control

20

3.5

Operating Status

The Operating Status is intended to provide the user with displayed information about what the con-

trol is calling for the system to do.

For example: The display indicates the chilled water valve is 68% open. On a new call for cooling, it

takes several seconds for the valve to travel from full closed to 68% open. So when the display reads

68%, it may take a few seconds for the valve to actually open 68%. Also, if the display indicates a com-

pressor is operating but the compressor has not turned on yet, it may be off because of the short cycle

control (see 4.4.1 - Short Cycle Control).

3.6

View/Set Control Setpoints

Control setpoints can be reviewed and/or changed through the display. Refer to the following table to

see the list of default setpoints and their allowable ranges.

3.7

System Setup

Selecting SYSTEM SETUP will step to the following menu:

• SETUP OPERATION
• SELECT OPTIONS
• CALIBRATE SENSORS
• CALIBRATE VALVE ACTUATOR
• SELECT CONTROL ALGORITHM (chilled water or SCR Reheats only)
• SELECT HUMIDITY SENSING MODE
• SET STATUS DISPLAY
• CHANGE PASSWORDS

3.7.1 Setup Operation

The SETUP OPERATION menu permits the review and/or adjustment of the unit configuration. This

may include:

Cold Start Delay

This feature, also referred to as Positive Start or Winter Start Kit, allows for the low pressure switch

to be ignored for the programmed time during a cold start of the compressor. Entering a “0” for this

time will bypass this feature. A “1” will bypass the low pressure switch for one minute, a “2” for two

minutes, etc. The programmed value can be from 0 to 3 minutes. This delay is factory set to 0 for

water cooled, glycol cooled, and GLYCOOL units. Typically, only air cooled units need a “Winter

Start” time.

NOTE
There may be some time lapse before a specific component matches the displayed number.

Table 8

Default setpoints and ranges

Setpoint

Default

Range

Temperature Setpoint

72

°

F

40 to 90

°

F (5 to 32

°

C)

Temperature Sensitivity

2.0

°

F

1 to 9.9

°

F (0.6 to 5.6

°

C)

Humidity Setpoint

50%

20 to 80% RH

Humidity Sensitivity

5%

1 to 30% RH

High Temperature Alarm

80

°

F

35 to 95

°

F (2 to 35

°

C)

Low Temperature Alarm

65

°

F

35 to 95

°

F (2 to 35

°

C)

High Humidity Alarm

60%

15 to 85% RH

Low Humidity Alarm

40%

15 to 85% RH