Auto restart delay, Ir flush overfill (infrared humidifiers only), Chilled water/hot water/econ-o-coil flush – Liebert CHALLENGER 3000 User Manual

Page 29: Display in degrees, Default settings and ranges, Table 9 setup functions, default values and ranges, Table 9, Setup functions, default values and ranges

Advertising
background image

Operation with Advanced Microprocessor with Graphics Control

21

Auto Restart Delay

This feature allows for the unit to restart automatically after a loss of power. The programmed value

is .1 minute (6 seconds) intervals. A programmed value of zero (0) would require the user to manually

press the ON/OFF switch to start the unit, i.e. no auto restart. The purpose of this feature is to pre-

vent several units from starting at the same time after a loss of power. The message “Restart Delay --

Please Wait” will be displayed when the system is in the auto restart mode. Liebert suggests pro-

gramming multiple unit installations with different auto restart times.

IR Flush Overfill (infrared humidifiers only)

An autoflush system automatically controls a water makeup valve to maintain proper level in the

infrared humidifier water pan during humidifier operation. If humidification is needed and 30 hours

have elapsed since the last time the humidifier was on, then the humidifier is held off until the valve

completes an initial fill of the humidifier pan. This pre-fill is about 15 seconds. The valve continues to

fill and flush the pan for about 4 minutes.
During humidifier operation, with the flush rate set at the default of 150%, the valve is opened peri-

odically to add water to the pan (about 40 seconds for every 9-1/2 minutes of humidifier operation).

This adds enough water to the pan to cause about a third of the total water used to be flushed out the

overflow standpipe located in the humidifier pan. This flushing action helps remove solids from the

pan. The flush rate is adjustable from 110% to 500%. If the water quality is poor, it may be desirable

to increase the water flushing action above the normal 150% rate. Also, if the supply water pressure

is low, the flush rate adjustment can be increased so that sufficient water level is maintained during

humidification.

Chilled Water/Hot Water/Econ-O-Coil Flush

This feature will flush the respective coil for 3 minutes after the programmed number of hours of

non-use. For example, if the flush time is programmed with 24 hours on a hot water reheat type sys-

tem, and heating is not required for a 24 hour period, the hot water valve will be opened for 3 minutes

to allow the coil to be flushed. The programmed value can be from 0 (no flush) to 99 (99 hours of

non-use).

Display in Degrees

The control can be set to display readings and setpoints in either degrees Fahrenheit (F) or

Celsius (C).

Default Settings and Ranges

The following table lists the setup functions, their factory default values, and the allowable ranges for

which they can be programmed.
Table 9

Setup functions, default values and ranges

Function

Default

Range

Cold Start Time Delay*

3

0 to 3 min (0 = no delay)

Restart Time Delay

0.1

0 to 9.9 min (0 = manual restart)

Infrared Fill Rate

150

110 to 500%

Chilled/Hot Water Coil Flush

24

0 to 99 hrs (also Econ-O-Coil)

C/F Degrees

F

C or F

*Factory set to 0 for water cooled, glycol, and GLYCOOL units.