Component Operation and Maintenance

43

Firestat

The optional firestat is a bimetal operated sensing device with a normally closed switch. This device

will shut down the entire unit when the inlet air temperature exceeds a preset point. It is connected

between terminals 1 and 2 at plug P39.

Smoke Detector

The optional smoke detector power supply is located on the base of the upflow units, and at the top of

downflow units. It is constantly sampling return air through a tube. No adjustments are required.

Water Detection Sensor

The optional water detection devices available are a point leak detection sensor and a zone leak detec-

tion kit.

Figure 7

Liebert leak detection units

The point leak detection sensor provides leak detection at a critical point. A simple two-wire connec-

tion signals the alarms at a Liebert environmental unit or at a monitoring panel. Run wires to the

Liebert unit and connect them to terminals 24 and 51, 55 or 56. Use NEC Class 2, 24V wiring. The

sensor contains a solid state switch that closes when water is detected by the twin sensor probes. The

sensor is hermetically sealed in all thread PVC nipple and is to be mounted where water problems

may occur. The sensor should be located 6-8 feet (2-2.5m) from the environmental control unit in a

wet trap or near a floor drain. It should not be mounted directly under the unit.

Figure 8

Recommended liquid sensor locations

!

CAUTION

Do not use near flammable liquids or for flammable liquid detection.

Liquitect Point Leak

Detection Sensor

LT460 Zone Leak

Detection Kit