Table 24

Dehumidification troubleshooting

Symptom

Possible Cause

Check or Remedy

No dehumidification

Control not calling for

dehumidification

Check monitor status.

Compressor contactor not pulling in

See 6.4.8 - Compressor Functional

Check and Table 23.

Compressor won't run; fuse blown or

CB tripped

See 6.4.8 - Compressor Functional

Check and Table 23. Check fuses or

CBs and contacts. Check line voltage

Table 25

Glycol pump troubleshooting

Symptom

Possible Cause

Check or Remedy

Suddenly stops pumping

Clogged strainer or impeller

Clean out debris.

Suddenly slow pumping

Clogged impeller, diffuser, or line

Clean out debris and use strainer.

Excessive leakage around the pump

shaft while operating

Worn seal or packing

Replace seal or packing.

Performance poor

Worn impeller or seal

Replace with new impeller or seal.

Suction lift too high

Relocate pump closer to supply.

Motor not up to speed; low voltage

Larger lead wires may be required.

Check for proper line voltage (±10%).

Worn bearings

Replace pump

Noisy operation

Worn motor bearings

Replace pump

Low discharge head

Throttle discharge-improve suction

conditions.

Debris lodged in impeller

Remove cover and clean out.

Cavitating pumps

Adjust system pressures.

Table 26

Infrared humidifier troubleshooting

Symptom

Possible Cause

Check or Remedy

No humidification

Humidifier pan not filling

Check water supply.
Check fill valve operation
Check drain stand pipe adjustment
Check for clogged waterline

Control not calling for humidity

Check monitor status

Humidity contact not pulling in

Check visually. If contact is made,

check line voltage after contactor and

fuses or CBs.
Check for open humidifier safety stat.

Jumper between terminals P35-6 and

P35-15. If contactor pulls in, replace

safety. Remove jumper.

Humidifier bulb burned out

Replace bulb. Loosen lead on old

bulb. Trim excess lead length on new

bulb to avoid shorts.