2.5.4 Change Passwords

The display prompts you to enter a three digit password when making changes. The system includes

two (2) passwords, one for setpoints and one for setup. The system allows the passwords to be changed

by first entering the present password, factory set as “123” for setpoints and “321” for setup. The pass-

word function provides system security, so only personnel authorized to make changes should know

the passwords. If unauthorized changes are being made, the passwords may be compromised and new

ones should be selected. The password function can be disabled by setting DIP switch 8 to OFF.

2.6

Date and Time

The current date and time is available through the display. This feature allows the date and time to

be read or changed and is accessed by selecting “DATE AND TIME” from the Main Menu.
The “DATE AND TIME” is used only by the control for recording the Alarm History.

2.7

Status Display

The Status Display selected from the Main Menu is the same Status Display that is normally on the

screen. While the Main Menu is displayed, you can press the MENU/ESC key to return to the Status

Display.

2.8

Control Circuit Board

The control circuit board is located inside the unit behind the LCD display and control key panel.

Open the front panel for access to the board.
The control board includes an adjustment for LCD display contrast, nonvolatile memory, DIP

switches (which should not require customer changes), control output LEDs and jumpers for board

configuration. The jumpers should be placed as follows:

P5—removed
P12—removed
P19—installed on Pins 1 and 2
P47—installed on Pins 1 and 2
P48—installed on Pins 1 and 2
P50—all jumpers installed for 4-20 mA analog inputs. See 4.5.1 - Connecting the Analog Sen-

sors for other configurations
P51—removed

2.8.1 LCD Display Contrast

The level of contrast due to viewing angle of the LCD display can be adjusted using a small thumb

wheel at the upper left of the control board just under the cable going to the display. The control is

labeled R6.

NOTE
The clock uses the 24 hour system (For example: 17:00 would be 5:00 PM). The date and time

are backed up by battery.

NOTE
The system automatically returns to the Status Display in five minutes if no

control keys are pressed.

NOTE
The LED backlighting on the text (4 x 20) display is always lit.