4 refrigeration system, 1 suction pressure, Table 18 suction pressures – Liebert CHALLENGER 3000 User Manual

Page 54: 2 discharge pressure, Table 19 discharge pressures, 3 superheat, Refrigeration system, Suction pressure, Discharge pressure, Superheat

Advertising
background image

Component Operation and Maintenance

46

6.4

Refrigeration System

Each month, the components of the refrigeration system should be inspected for proper function and

signs of wear. Since, in most cases, evidence of malfunction is present prior to component failure, peri-

odic inspections can be a major factor in the prevention of most system failures.
Refrigerant lines must be properly supported and not allowed to vibrate against ceilings, floors or the

unit frame. Inspect all refrigerant lines every six months for signs of wear and proper support. Also

inspect capillary and equalizer lines from the expansion valve and support as necessary.
Each liquid line has a sight glass that indicates liquid refrigerant flow and the presence of moisture.

Bubbles in the sight glass indicate a shortage of refrigerant or a restriction in the liquid line. The

moisture indicator changes from green to yellow when moisture is present in the system.

6.4.1 Suction Pressure

Suction pressure will vary with load conditions. The low pressure switch will shut the compressor

down if suction pressure falls below the cut-out setting. High suction pressure reduces the ability of

the refrigerant to cool compressor components and can result in compressor damage. Minimum (pres-

sure switch cut-out setting) and maximum (design operating) suction pressures are in Table 18.

6.4.2 Discharge Pressure

Discharge Pressure can be increased or decreased by load conditions or condenser efficiency. The high

pressure switch will shut the compressor down at its cut-out setting. Refer to Table 19, below.

6.4.3 Superheat

Superheat can be adjusted by the Thermostatic Expansion Value (TEV). To determine superheat:
1. Measure the temperature of the suction line at the point the TEV bulb is clamped.
2. Obtain the gauge pressure at the compressor suction valve.
3. Add the estimated pressure drop between bulb location and suction valve.
4. Convert the sum of the two pressures to the equivalent temperature.
5. Subtract this temperature from the actual suction line temperature. The difference is superheat.

Table 18

Suction pressures

System

Minimum

PSIG (kPa)

R–22

Maximum

PSIG (kPa)

R–22

Air w/FSC

(Fan Speed Control)

15 (103)

90 (620)

Air w/Lee-Temp Control

(Floodback head

pressure control)

20 (137)

90 (620)

Water Cooled

20 (137)

90 (620)

Glycol Cooled

20 (137)

90 (620)

Table 19

Discharge pressures

System Design

Discharge Pressure

PSIG (kPa)

Air Cooled

260 (1795)

Water/Glycol Cooled

65-75

°

F (18-24

°

C) fluid

210 (1450)

85

°

F (29

°

C) fluid

225 (1550)

115°F (46°C) fluid

295 (2035)

Maximum

330 (2275)

High Pressure Cut-Out

360 (2482)

Advertising