11 analog/digital inputs, 1 read analog inputs, 2 setup analog inputs – Liebert CHALLENGER 3000 User Manual

Page 34: Slope, Intercept, Text, 3 read digital inputs, 4 setup digital inputs, 12 view run hours log, Analog/digital inputs

Advertising
background image

Operation with Advanced Microprocessor with Graphics Control

26

3.11 Analog/Digital Inputs

Selecting ANALOG/DIGITAL INPUTS steps to the following menu:

• READ ANALOG INPUTS
• SETUP ANALOG INPUTS
• READ DIGITAL INPUTS
• SETUP DIGITAL INPUTS

3.11.1 Read Analog Inputs

The four (4) analog sensor inputs can be monitored from the display. The inputs are filtered, then dis-

played along with the text label assigned during setup.

3.11.2 Setup Analog Inputs

For installation of analog sensors, see Analog Setup on page 11.
After selecting a compatible sensor and properly wiring it to the terminals, set the control to monitor

the sensor according to the following instructions.

Slope

The slope is a multiplier used to scale the input signal. The slope can be positive (rising) or negative

(falling) and can range from 0 (resulting in a horizontal line) to ±999. The slope for a 0-5 volt input is

per 1 volt input; for 0-10 volt input, it is per 2 volt input; and for 4-20 mA, it is per 4 mA input. For

example, assuming an intercept of 0, for a 0-10 volt sensor input with a slope of 50, an input of 1 volt

would be displayed as 25: 1x(50/2); 2 volts would be 50: 2x(50/2); 3 volts would be 75: 3x(50/2); etc.

Intercept

The intercept is an offset from point 0 corresponding to 0 volts or 0 mA input. The intercept can be

positive or negative and can be a point from 0 to ±999. Adding an intercept of 100 to the slope example

above, 1 volt would be 125: 100 + (1x[50/2]); 2 volts would be 150: 100 + (2x[50/2]); 3 volts would be

175: 100 + (3x[50/2]); etc.

Text

You may enter a custom label for each analog input. The text label can be 20 characters in length

including any of the following:

ABCDEFGHIJKLMNOPQRSTUVWXYZ#%*-0123456789, or space.

3.11.3 Read Digital Inputs

The four custom alarm inputs can be defined to be digital inputs. Digital inputs are used to sense cus-

tomer devices for status display purposes only and will not activate the audible alarm.

3.11.4 Setup Digital Inputs

A digital input is enabled by defining one of the four custom alarms to be STATUS ONLY type in the

alarm setup screen. The digital input is given a name by specifying it to be one of the optional alarms

or a custom text alarm. See 3.4.3 - Setup Alarms and 3.4.4 - Setup Custom Alarms.

3.12 View Run Hours Log

Selecting VIEW RUN HOURS LOG will step to the following menu:

• VIEW 24 HOUR RUN TIME HISTORY
• VIEW TOTAL RUN HOURS

NOTE
For a 4-20 mA input sensor, if the desired reading at 4 mA input is 0, then an intercept

of -1 x slope would be required. For example, assuming a slope of 50, the formula would

be ([-1 x 50] + 4 x [50/4]) = 0. The intercept is -50.

Advertising