Operation with Advanced Microprocessor with Graphics Control

28

3.13.2 Nonvolatile Memory

All critical information is stored in nonvolatile memory. Setpoints, setup parameters, and component

run hours are kept inside the microcontroller in EEPROM. Information retained for data logging,

24 hour component run hour graphs, alarm history, and the water detection floor plan is kept in non-

volatile RAM.

3.13.3 DIP Switches

Equipment options are selected and enabled using DIP switches 1 to 7. These are located at the upper

left of the control board and are labeled SW1. Switch 1 is at the top. These switches are factory set

and should not require any user changes. The setting and function of the switches can be read from

the LCD (see 3.8.4 - DIP Switches).

3.13.4 Control Outputs

Active control outputs are indicated with LEDs on the lower section of the control board. Each LED is

lit if the control output is active (on). Use these LEDs to assist in troubleshooting the system.
Table 12

Control output LEDs

LED

Control Output

R5

Heat Rejection

LLSV

Liquid Line Solenoid Valve

HGBP

Hot Gas By-Pass

C1

Compressor

RH1

Reheat Stage 1 or Hot Gas, Hot Water Reheat Solenoid

or SCR Reheats

RH2

Reheat Stage 2

HUM

Humidifier

FAN

Main Fan

HMV

Humidifier Make-Up Valve

LLSV2

Part Coil Solenoid Valve