The zone leak detection kit provides leak detection for a defined zone. This kit is ideal for perimeter

sensing or serpentine coverage of small areas. A simple, two-wire connection signals the alarms at a

Liebert environmental unit or at a monitoring panel. Run wires to the Liebert unit and connect them

to terminals 24 and 51, 55 or 56. The sensor utilizes Liebert's LT500Y leak detection cable. The kit is

offered with five different lengths of cable sized specifically for the type of Liebert Environmental unit

(see matrix below). Refer to matrix below for the recommended location of leak detection cable.

Remote Shutdown

A connection point is provided for customer supplied remote shutdown devices. This terminal strip is

located at the top of upflow units, and at the base of downflow units. Terminals 37 and 38 on the ter-

minal strip are jumpered when no remote shutdown device is installed.

6.2

Filters

Filters are usually the most neglected item in an environmental control system. To maintain efficient

operation, they should be checked monthly and changed as required. Because replacement intervals

vary with environmental condition and filter type, each unit is equipped with a filter clog switch. This

warns of restricted airflow through the filter compartment by activating the Change Filter alarm.
Turn power off before replacing filters.
Challenger 3000 filters are 28-1/2" by 29-1/2", either 2" or 4" thick, plus an optional 2" thick pre-filter.

The filter is replaced from the front of the unit. On upflow units, the filter is vertical, in front of the

lower compartment. Pull the filter out toward you to remove it. On downflow units, the filter is hori-

zontal, above the electrical panel. Slide the filter out toward you to remove it.
After replacing the filter(s), test the operation of the filter clog switch. Turn the adjusting screw

counter clockwise to trip the switch — this will energize the Change Filter alarm. To adjust the

switch proceed as follows: With the fan running, set the switch to energize the light with clean filters.

The unit panels must all be in place and closed to accurately find this point. Then turn the adjusting

knob one turn clockwise, or to the desired filter change point.

Table 16

Zone leak detection kit installation scenarios

Scenarios

Upflow Unit

Detection

around

entire unit

Upflow Unit

Detection on sides

and

in front of unit

Downflow Unit

Detection

around

entire unit

Downflow Unit

Detection on sides

and

in front of unit

Distance From Unit

Distance:

In back

On sides

In front

2 ft

2 ft

2 ft

No cable behind

2 ft

2 ft

1 ft

1 ft

6 ft

No cable behind

1 ft

6 ft

Unit

(footprint-

in.)

Part Number

Challenge

r

(32.5 x

32.5)

LT460-Z30

LT460-Z20

LT460-Z30

LT460-Z25

2-ft clearance

in front

2-ft clearance

in front

6-ft clearance

in front

6-ft clearance

in front