Physical connections, Setup, Calibration – Liebert CHALLENGER 3000 User Manual

Page 44

Advertising
background image

System Performance with Advanced Microprocessor Controls

36

Physical Connections

Figure 6 shows the 4-20 mA output of LT750 connected to Analog Input #1 (41 and 42) on the exter-

nal inputs terminal strip. This strip is provided on units ordered with analog inputs. (If this strip is

not installed, there is a field installation kit available from your Liebert representative.)
The 4-20 mA output of the LT750 must be connected to the first analog input, as shown.

TB4 is the water detected relay output. It can be connected to any one of the four special alarm inputs.

TB5 is the cable fault relay output. It can also be connected to any one of the four special alarm

inputs.

Setup

(The following description assumes the wiring connections as shown above.) First, verify that special

alarms 1 and 2 are ENABLED to either WARNING or URGENT type. Do this by selecting VIEW/SET

ALARMS from the Main Menu. Then, select SETUP ALARMS. Follow the instructions on the display

to select the required type for CUSTOM ALARM #1 and CUSTOM ALARM #2 if not already set.
Next, select the alarm message for CUSTOM ALARM #1 and #2. From the Main Menu, select VIEW/

SET ALARMS. Then, select SETUP CUSTOM ALARMS. Then, select SETUP CUSTOM ALARM

TEXT. Define CUSTOM ALARM #1 to be CUSTOM 1. (CUSTOM 1 is the default message that will be

displayed if a message has never been programmed.) Next, select the text for custom alarm #2 to be

WATER UNDER FLOOR. Now, change the message CUSTOM 1 to LT750 CABLE FAULT. This is

done by selecting the CHANGE CUSTOM TEXT 1 menu item in the SETUP CUSTOM ALARMS

menu. Follow the instructions on the screen to change the message.
The slope and intercept values of Analog Input #1 are used to calculate the location of water. These

values should initially be set to zero. The default values are zero, but it may be a good idea to verify

those values. They can be viewed by selecting ANALOG/DIGITAL INPUTS from the Main Menu,

then SETUP ANALOG INPUTS.
See 3.4.6 - Setup Water Detect Floor Plan for more information.

Calibration

Calibration should not be required for most installations. The accuracy of this display is approxi-

mately 1%.
The display is calibrated by the slope and intercept values of Analog Input #1. The position of the

water is calculated from the analog output of the LT750 using this formula:

position = analog reading/full scale reading x (measured length + slope) + intercept

position is the distance from the LT750 to the position of the detected water.
measured length is the length of the cable which is calculated automatically when the layout is

defined. The units for these values are in floor tiles.
The intercept value read from Analog Input #1 is added to the measured position of a water indication

to determine which tile to highlight. For example, if water is displayed under the seventh tile but

determined to be under the fifth tile, set the offset value to -2 tiles. Use the intercept value to correct

errors close to the start of the cable.
Accuracy errors farther out on the cable should be corrected using Analog Input #1's slope value. This

value effectively adjusts the measured length of the cable. Increasing the effective length of cable will

increase the distance of the water and move the highlighted tile farther along the cable, and vice

versa. Unlike the intercept, which adjusts by the same amount for all locations on the cable, the slope

increases its effect for larger distances.
The best procedure to calibrate the cable would be to first simulate water close to the LT750, about

five tiles out. Adjust the intercept to get the correct reading. Next, simulate water five tiles from the

end. Adjust the slope to get the correct reading.

Advertising