Chapter Four--Wiring

2. At the RPS Slave panels, strip the cable sheath back

approximately 20 inches. Cut the conductors for Left Bus
B, Left Bus A, – and + down to approximately 4 inches and
terminate them in the Left Bus screw-terminal header from
left to right. Terminate the remaining two conductors in
the Right Bus B and Right Bus A positions of the Right Bus
screw-terminal header.

3. Using two cut lengths of 18 AWG wire, install jumpers from

Left Bus – and + to Right Bus – and +. Right Bus will not
operate without these jumpers installed to provide 24VDC
power and common.

4. Set the slave address selectors as follows:

Table 4-2

Left Control Bus

Right Control Bus

Panel #2

2

3

Panel #3

4

5

Panel #4

6

7

Master Panel

Slave Panel 2

Slave Panel 3 Slave Panel 4