139-0498-01.26

Chapter Five--Control Setup

26

Figure 5-3: Interface options

NetBios Name

The NetBios name defaults to LynTecRPC. Each
master panel in your system should be assigned a
unique NetBios name. After names are assigned the
user can access the system web page by entering the
NetBios name into the web browser instead of using
the IP address.

Port Type

The port type section is used to select the preferred serial
communication protocol. The controller defaults to Ethernet
(TCP/IP) for setup but can be controlled in conjunction with
RS-232, RS-485 or DMX-512 protocols.

For RS-485 operation the device address must be entered in
the adjacent fi eld.

For DMX operation use the following steps:

Enter the fi rst individual breaker address. All motorized
breakers will be automatically assigned to consecutive
addresses. Zone control is not availible with DMX operation.

Please note that selecting DMX control will disable web
control.