Lyntec RPC User Manual

Page 43

Advertising
background image

139-0498-01.43

43

Appendix A

6

Con

fi

gure the digital I/O port.

Note: If the Emergency Shutoff feature is selected, the

fi rst

position in the Onboard

fi eld

(on

the Controller) is automatically assigned to that.

A.

R

ename each contact closure as

desired

B

.

Click the M (merge) button at the right side of the

fi

rst of the

two ports used. The name bo

x

and M button in the second port should turn gr

ay

and the Action

selections should default to Momentary NO

. (normally open)

C.

Ensure that both of the Action selections for both ports are set to Momentary NO

.

D

.

Click the “Sa

ve

Changes” button

at the top of the Onboard I/O bo

x.

7

Assign the contact closure to a z

one

in the “P

anel” (SETUP

==>P

ANELS)

screen:

A.

In the Z

ONE CONTROL bo

x under

“CC/Schedule”

, choose which

contact closure to assign to an

y

zone using the drop down bo

x.

B

.

Enable the z

one by selecting

Sequenced or Grouped oper

ation

under “Name/Seq”

.

C. Sa

ve

changes.

8

V

erify proper oper

ation of y

our

S

witch Set:

A.

Press the ON switch. Break

ers in

the selected z

one should immedi-

ately begin actuating.

B

.

The ON indicator should

fl ash

steadily until all of the break

ers

are in the on state.

C.

When the z

one has completed,

the ON indicator should remain constantly lit.

D

.

Press the OFF switch. Break

ers in

the selected z

one should immedi-

ately begin actuating.

E.

The ON indicator should

fl ash

steadily until all of the break

ers

are in the off state.

F.

When the z

one has completed,

the ON indicator should remain constantly dark. Note: When using two illuminate pushbut

-

tons the OFF indicator will remain constantly lit when the z

one has

completed. (OFF indicator will extinguish immediately when ON is pressed again.)

Advertising