Chapter Five--Control Setup

36

Individual Momentary Contact ON and
OFF Pushbuttons

Using a standard LynTec SS-2 Switch Set with illuminated ON
switch or two illuminated pushbuttons:

Confi gure the Digital I/O port and link it to a zone as follows:

1. Follow the previous instructions for naming the contact

closure and setting closure type.

2. Click the M button at the right side of the fi rst of the two

ports used. The name box and M button in the second port
should turn gray and the Action selections should default to
Momentary NO. (normally open)

3. Ensure that both of the Action selections for both ports are

set to Momentary NO.

4. Enter a name in the text fi eld of the CC used that is

indicative of the zone it will control.

5. Click the “Save Changes” button at the top of the Onboard

I/O box.

6. Follow the previous instructions for assigning a contact

closure to a zone, selecting the merged ports.

7. Click the Save Changes button in the upper left corner of

the Panels page.

Verify proper operation of your Switch Set:

1. Press the ON switch. Breakers in the selected zone should

immediately begin actuating.

2. The ON indicator should fl ash steadily until all of the

breakers are in the on state.

3. When the zone has completed, the ON indicator should

remain constantly lit.

4. Press the OFF switch. Breakers in the selected zone should

immediately begin actuating.

5. The ON indicator should fl ash steadily until all of the

breakers are in the off state.

6. When the zone has completed, the ON indicator should

remain constantly dark. Note: When using two illuminate
pushbuttons the OFF indicator will remain constantly
lit when the zone has completed. (OFF indicator will
extinguish immediately when ON is pressed again.)