RPC Contact Closure Wiring Instructions

1

2

3

4

5

6

Left Bus

IN

24V

OUT

Digital I/O

NO

C

NC

+

NO

C

NC

ON

OFF

OFF

LynTec

RPC

Contact Closure Wiring Instructions

1

Con

fi

rm that RPS (sla

ve) panels are

properly connected to the master as indicated in the “RPC to RPS Wiring Instructions” bulletin.

2

Complete all the steps in the “RPC Quick Start Guide”

.

Using a standard L

ynT

ec S

S-2 S

witch

Set with illuminated ON switch. (F

or

other types of switches, consult CH 4 of the instruction bulletin for wiring diagr

ams.)

3

Wire the ON switch to a digital I/O port on the left edge of the Controller board as follows:

A.

Connect the 24VDC Common (center terminal of the I/O port) to the C pin of the ON switch.

B

.

Connect the Input terminal (arrow pointing tow

ards header)

to the NO pin of the ON switch.

C.

Connect the Output terminal (arrow pointing aw

ay

from

header) to the – pin of the ON switch.

D

.

Connect a jumper between the C pin and the + pin of the ON switch.

4

Wire the OFF switch to a digital I/O port on the left edge of the Controller board as follows:

A.

Connect the 24VDC Common terminal to the C pin of the OFF switch.

B

.

Connect the Input terminal to the NO pin of the OFF switch

Note: If using emergency override features,

fi

re alarm contact closures

must be wired into port 1.

5

On the RPC web page, go to

the contact closure page. (SETUP

==>

CONT

ACT CL

OSURES)