Figure 4-11: rpc mechanical drawing – Lyntec RPC User Manual

Page 21

Advertising
background image

139-0498-01.21

21

Chapter Four--Wiring

Figure 4-11: RPC Mechanical Drawing

Low Voltage Cabinet

56.00"

28.00"

2.00"

15.00"

28.00"

50.00"

3.00"

Feed

4/0 max.

46 positions

14 - 4 ga.

Isolated

Technical

Ground

Bar

High voltage interior may be

field inverted for top feed

139-0500-00 RPC 341 Mechanical 9/25/08

8.50"

Standard RPC Main Breaker:

225 Amp - 65k AIR - MJG32225

Main Breaker options - Part # suffix

-MHG3110, MHG3125,

-MJG3150, -MJG3175, -MJG3200

(all 65k Amp Interrupt Rating)

Main Breaker wire:

3/0-350 kcmil Aluminum or Copper
200% Neutral has one feed lug that

accepts two 350 kcmil wires.

Feed

2/0 max.

Square D NF MB Panel

with LynTec sidecars.

Outside dimensions

28" w x 56" h x 6" d

Power Supply, Buffer

and VoltageTransducer

Multi-Panel

Expander Board

Master Controller

Optional - Digital I/O

Expander Boards

Breaker

Control
Busses

1.5" I.D.

wiring

access

nipples

between

sidecars

and

panelboard

Advertising