IAI America MSEP User Manual
Page 124
3.4 Fieldbus
Type
Address Map
116
(3) I/O signal assignment
(ON = Applicable bit is “1”, OFF = Applicable bit is “0”)
Signal Type
Bit
Symbol
Description
Details
Target
Position
32 bits
Data
–
32-bit signed integer indicating the current position
Unit: 0.01mm
Available range for Setting: -999999 to 999999
Set the target position with the value from the home
position.
(Example) If +25.40mm, input 000009EC
H
(2540 in
decimal system).
(Note) Input the negative value using a compliment of 2.
3.8.1 (22)
Positioning
Width
32 bits
Data
–
32-bit integer
Unit: 0.01mm
Available range for Setting: 0 to 999999
(Example) If 25.40mm, input 000009EC
H
(2540 in
decimal system).
This register value has two meanings depending on the
operation type.
1) Positioning operation
Range for positioning complete against the target
position
2) Pressing operation
Pressing width (Pressing operation distance)
A pressing operation is performed when PUSH Signal in
the control signals is ON.
3.8.1 (22)
Command
Speed
16 bits
Data
–
16-bit integer
Unit: 1.0mm/sec or 0.1mm/sec (It is set to 1.0mm/sec in
the initial setting.)
A change of the unit is to be conducted on Gateway
Parameter Setting Tool.
Available range for Setting: 1 to 65535
Specify the speed at which to move the actuator.
(Example) If 254.0mm/sec, input 09EC
H
(2540 in decimal
system).
It may cause an alarm or a malfunction if executing a
movement command with 0 or a value more than the
maximum speed of the actuator.
3.8.1 (22)
Acceleration/
Deceleration
16 bits
Data
–
16-bit integer
Unit: 0.01G
Available range for Setting: 1 to 300
Specify the acceleration/deceleration at which to move
the actuator. The acceleration and deceleration will be
the same value.
(Example) If 0.30G, input 001E
H
(30 in decimal system).
It may cause an alarm or a malfunction if executing a
movement command with 0 or a value exceeding the
maximum acceleration/deceleration of the actuator.
3.8.1 (22)
P
LC
O
ut
pu
t䎃
Pressing
Current
Limit
16 bits
Data
–
16-bit integer
Unit: %
Available range for Setting: 0 to 100
Indicate the current value for pressing operation.
(Example) If “50%”, input “007F
H
”.
The pressing range available for indication differs
depending on the actuator (Refer to the catalogue or
instruction manual for the actuator). It may cause an
alarm or a malfunction if executing a movement
command with a value more than the maximum pressing
current.
3.8.1 (22)