Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 132

Advertising
background image

132

EVAPORATOR-FAN MOTOR PROTECTION — A manu-

al reset, calibrated trip, magnetic circuit breaker protects

against overcurrent. Do not bypass connections or increase the

size of the breaker to correct trouble. Determine the cause and

correct it before resetting the breaker.
CONDENSER-FAN MOTOR PROTECTION — Each

condenser-fan motor is internally protected against over-

temperature. They are also protected against a severe over-

current condition by manual reset, calibrated trip, magnetic cir-

cuit breakers on a common circuit. As with the circuit breakers,

do not bypass connections or increase breaker size to correct

trouble. Determine the cause and correct it before resetting the

breaker.
HIGH-PRESSURE SWITCHES — See Fig. 51 for compres-

sor mounting locations. Settings for these switches are shown

in Tables 97A and 97B. If either switch trips, that refrigerant

circuit will be automatically locked out by the controls. To re-

set, recycle control power to unit.

Table 97A — Pressure Switch Settings (psig)

Table 97B — Pressure Switch Settings (Pa)

Relief Devices —

All units have relief devices to protect

against damage from excessive pressures (i.e., fire). These de-

vices protect the high and low side.

Control Circuit, 115 V —

This control circuit is protect-

ed against overcurrent by a 5-amp (sizes 030-090) or 9-amp

(size 105) circuit breaker. Breaker can be reset. If it trips, deter-

mine cause of trouble before resetting.

Control Circuit, 24 V —

This control circuit is protected

against overcurrent by a 3.2-amp circuit breaker. Breaker can be

reset. If it trips, determine cause of trouble before resetting.

Gas Heat (48Z Only)

LIMIT SWITCHES — The maximum supply-air temperature

is controlled by a limit switch located in the gas section. The

limit is designed to trip at 100 F above the maximum tempera-

ture rise.

When the limit trips, 2 flashes occur on the IGC board. The

gas valve is deenergized. After cooling, the system will reset

and fires gas again. If four trips occur, the system shuts down

into Lockout and 4 flashes occur on the IGC board. The system

must then be manually reset by power down and power up of

the unit.

LIMIT SWITCH THERMISTOR (Staged Gas Unit

Only) — The limit switch thermistor is a factory-installed

component. It is located next to the lower limit switch. The

limit switch thermistor senses temperature at limit switch loca-

tion and prevents the limit from tripping while the unit is oper-

ating at low airflow.
ROLLOUT SWITCH — This switch senses any flame or ex-

cessive heat in the main burner compartment and deenergizes

the gas valve. If this occurs, the gas heating system is locked

out (7 flashes on IGC board) until the rollout switch is reset

manually. Reset rollout switch manually by powering down

and powering up of the unit.

When the rollout switch trips, it usually indicates a flue

blockage. Inspect the unit for any obstruction in the flue sys-

tem, for holes in the flue box, a defective hall effect sensor, a

defective inducer motor, or a loose combustion blower.

Compressor Removal —

Access to the pump end of

the compressor is from the compressor side of the unit. Access

to the motor end of the compressor is from the inside of the

unit. All compressors can be removed from the compressor

side of the unit.

1. Disconnect power to unit; lockout power to compressor.
2. Close suction and discharge service valves.
3. Relieve refrigerant pressure into a refrigerant recovery

system.

4. Remove:

a. Fan-cycling pressure switch (FCPS)
b. High-pressure switch

5. Disconnect power wires at terminal box and disconnect

conduit.

6. Disconnect wires from crankcase heater.
7. Disconnect service valves from compressor.
8. Remove 4 locknuts securing compressor to the spring

assemblies.

9. Lift compressor off mounting bolts and remove.

Compressor Replacement —

Perform the following:

1. Reverse procedure in Compressor Removal section to

end of Step 4.

2. Reinstall service valves and safety switches, and tighten

to torques as listed:

3. Leak-check and evacuate system, recover refrigerant.
4. Recharge system per pre-start-up and start-up sequences.

Recheck oil levels.

5. Energize crankcase heater for 24 hours prior to restart of

system.

IMPORTANT: After a prolonged shutdown or service

job, energize the crankcase heaters for 24 hours before

starting the compressor.

SWITCH

CUTOUT

CUT-IN

High

426

± 7

320

± 20

SWITCH

CUTOUT

CUT-IN

High

2937

± 48

2206

± 138

Fig. 51 — Typical Compressor Overtemperature

and High-Pressure Switch Locations

IMPORTANT: All compressor mounting hardware and

support brackets removed during servicing must be rein-

stalled prior to start-up.

TORQUE

COMPRESSOR(S)

Tighten discharge valves to —

20-25 ft-lb (27- 34 N-m)
80-90 ft-lb (109-122 N-m)

06E-250, 06D-537
06E-265,275,299

Tighten suction valves to —

80- 90 ft-lb (109-122 N-m)
90-120 ft-lb (122-163 N-m)

06E-250, 06D-537
06E-265,275,299

Tighten the following fittings as specified —

120 in.-lb (13.5 N-m)

High-Pressure Switch

Advertising