Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 173

Advertising
background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53480039-01

Printed in U.S.A.

Form 48/50Z-5T CL-1

7-08

Replaces: 48/50Z-4T

ITEM

EXPANSION

RANGE

DEFAULT

SETTING

UNIT

UNIT CONFIGURATION

C.TYP

Machine Control Type

1 - 6 (multi-text strings)

4

CV.FN

Fan Mode (0=Auto, 1=Cont)

0 - 1 (multi-text strings)

1

RM.CF

Remote Switch Config

0 - 3 (multi-text strings)

0

CEM

CEM Module Installed

Yes/No

No

TCS.C

Temp.Cmp.Strt.Cool Factr

0 - 60 min

0

TCS.H

Temp.Cmp.Strt.Heat Factr

0 - 60 min

0

SFS.S

Fan Fail Shuts Down Unit

Yes/No

No

SFS.M

Fan Stat Monitoring Type

0 - 2 (multi-text strings)

0

VAV.S

VAV Unocc.Fan Retry Time

0 - 720 min

50

SIZE

Unit Size (30-105)

30 - 105

30

50.HZ

50 Hertz Unit ?

Yes/No

No

MAT.S

MAT Calc Config

0 - 2 (multi-text strings)

1

MAT.R

Reset MAT Table Entries?

Yes/No

No

MAT.D

MAT Outside Air Default

0 - 100‘%

20

ALTI

Altitude……..in feet:

0 - 60000

0

DLAY

Startup Delay Time

0 - 900 secs

0

AUX.R

Auxiliary Relay Config

0 - 3 (multi-text strings)

0

SENS

INPUT SENSOR CONFIG

SENSSPT.S

Space Temp Sensor

Enable/Disable

Disable

SENSSP.O.S

Space Temp Offset Sensor

Enable/Disable

Disable

SENSSP.O.R

Space Temp Offset Range

1 - 10

5

SENSSRH.S

Space Air RH Sensor

Enable/Disable

Disable

SENSRRH.S

Return Air RH Sensor

Enable/Disable

Disable

SENSFLT.S

Filter Stat.Sw.Enabled ?

Enable/Disable

Disable

COOL

COOLING CONFIGURATION

Z.GN

Capacity Threshold Adjst

-10 - 10

1

MC.LO

Compressor Lockout Temp

-25 - 55 dF

40

L.L.EN

Lead/Lag Operation ?

Yes/No

No

M.M.

Motor Master Control ?

Yes/No

No

HPSP

Head Pressure Setpoint

80 - 150 dF

113

A1.EN

Enable Compressor A1

Enable/Disable

Enable

A2.EN

Enable Compressor A2

Enable/Disable

Enable

B1.EN

Enable Compressor B1

Enable/Disable

Enable

B2.EN

Enable Compressor B2

Enable/Disable

Enable

CS.A1

CSB A1 Feedback Alarm

Enable/Disable

Enable

CS.A2

CSB A2 Feedback Alarm

Enable/Disable

Enable

CS.B1

CSB B1 Feedback Alarm

Enable/Disable

Enable

CS.B2

CSB B2 Feedback Alarm

Enable/Disable

Enable

HPS.A

CMPA1 Hi.Pr.Sw. Trip

365 - 415 PSIG

415

HPS.B

CMPB1 Hi.Pr.Sw. Trip

365 - 415 PSIG

415

H.SST

Hi SST Alert Delay Time

5 - 30 min

10

EDT.R

EVAP.DISCHRGE TEMP RESET

RS.CF

EDT Reset Configuration

0 - 3 (multi-text strings)

2

RTIO

Reset Ratio

0 - 10

3

LIMT

Reset Limit

0 - 20

^F

10

RES.S

EDT 4-20 ma Reset Input

Enable/Disable

Disable

CONTROLS SET POINT AND CONFIGURATION LOG

MODEL NUMBER:

Software Version

SERIAL NUMBER:

MBB

CESR131292--

DATE:

RCB

CESR131249--

TECHNICIAN:

ECB

CESR131249--

NAVI

CESR131227--

SCB

CESR131226--

CEM

CESR131174--

MARQ

CESR131171--

Advertising