Table 31 — Service Test

ITEM

EXPANSION

RANGE

UNITS

POINT

WRITE STATUS

TEST

Service Test Mode

ON/OFF

MAN_CTRL

STOP

Local Machine Disable

YES/NO

UNITSTOP

config

S.STP

Soft Stop Request

YES/NO

SOFTSTOP

forcible

FAN.F

Supply Fan Request

YES/NO

SFANFORC

forcible

INDP

TEST INDEPENDENT OUTPUTS

HUM.R

Humidifier Relay

ON/OFF

HUMR_TST

ALRM

Remote Alarm/Aux Relay

ON/OFF

ALRM_TST

FANS

TEST FANS

F.MOD

Fan Test Automatic?

YES/NO

FANAUTO

E.POS

Econo Damper Command Pos

%

ECONFANS

S.FAN

Supply Fan Relay

ON/OFF

SFAN_TST

I.POS

IGV Actuator Command Pos

0-100

%

IGVFNTST

S.VFD

Supply Fan VFD Speed

0-100

%

SGVFDTST

P.E.1

Power Exhaust Relay 1

ON/OFF

PE1_TST

P.E.2

Power Exhaust Relay 2

ON/OFF

PE2_TST

BP1.P

BP 1 Command Position

0-100

%

BLDPTST1

BP2.P

BP 2 Command Position

0-100

%

BLDPTST2

E.VFD

Exhaust Fan VFD Speed

0-100

%

EFVFDTST

CD.F.A

Condenser Fan Circuit A

ON/OFF

CNDA_TST

CD.F.B

Condenser Fan Circuit B

ON/OFF

CNDB_TST

CD.MM

Motormaster Condenser Fan

ON/OFF

PCFABTST

ACT.C

CALIBRATE TEST-ACTUATORS

ECN.C

Economizer Act.Cmd.Pos.

0-100

%

ECONOTST

E.CAL

Economizer Calibrate Cmd

YES/NO

ECONOCAL

ECN.A

Econ Act. Control Angle

read only

ECONCANG

EC2.C

Economzr 2 Act.Cmd.Pos.

0-100

%

ECON2TST

E2.CL

Economzr 2 Calibrate Cmd

YES/NO

ECON2CAL

EC2.A

Econ2 Act.Control Angle

read only

ECN2CANG

IGV.C

IGV Actuator Command Pos

0-100

%

SPIGVTST

I.CAL

IGV Act. Calibrate Cnd

YES/NO

IGV_CAL

IGV.A

IGV Act. Control Angle

read only

IGC_CANG

IGV.M

VFD-IGV Maximum Speed

0-100

%

STATPMAX

BP1.C

BP 1 Command Position

0-100

%

BLDG1TST

B1.CL

BP 1 Actuator Cal Cmd

YES/NO

BLDG1CAL

BP1.A

BP Act.1 Control Angle

read only

BP1_CANG

BP1.M

BP 1 Actuator Max Pos.

0-100

%

BP1SETMX

BP2.C

BP 2 Command Position

0-100

%

BLDG2TST

B2.CL

BP 2 Actuator Cal Cmd

YES/NO

BLDG2CAL

BP2.A

BP Act.2 Control Angle

read only

BP2_CANG

BP2.M

BP 2 Actuator Max Pos.

0-100

%

BP2SETMX

HTC.C

Ht.Coil Command Position

0-100

%

HTCLACTC

HT.CL

Heating Coil Act. Cal.Cmd

YES/NO

HCOILCAL

HTC.A

Heat Coil Act.Ctl.Angle

read only

HTCLCANG

HMD.C

Humidifier Command Pos.

0-100

%

HUMD_TST

HM.CL

Humidifier Act. Cal.Cmd

YES/NO

HUMIDCAL

HMD.A

Humidifier Act.Ctrl.Ang.

read only

HUMDCANG

COOL

TEST COOLING

E.POS

Econo Damper Command Pos

0-100

%

ECONCOOL

SP.SP

Static Pressure Setpoint

0-5

"H2O

SPSP_TST

CL.ST

Requested Cool Stage

0-n

CLST_TST

LD.LG

Lead/Lag Select Test

LEAD/LAG

LL_TST

A1

Compressor A1 Relay

ON/OFF

CMPA1TST

U1.A1

Unloader 1 - Comp A1

ON/OFF

UNL1_TST

U2.A1

Unloader 2 - Comp A1

ON/OFF

UNL2_TST

A2

Compressor A2 Relay

ON/OFF

CMPA2TST

B1

Compressor B1 Relay

ON/OFF

CMPB1TST

U1.B1

Unloader 1 - Comp B1

ON/OFF

UNL3_TST

U2.B1

Unloader 2 - Comp B1

ON/OFF

UNL4_TST

B2

Compressor B2 Relay

ON/OFF

CMPB2TST

HEAT

TEST HEATING

HT.ST

Requested Heat Stage

0-n

HTST_TST

HT.1

Heat Relay 1

ON/OFF

HS1_TST

HT.2

Heat Relay 2

ON/OFF

HS2_TST

HT.3

Relay 3 W1 Gas Valve 2

ON/OFF

HS3_TST

HT.4

Relay 4 W2 Gas Valve 2

ON/OFF

HS4_TST

HT.5

Relay 5 W1 Gas Valve 3

ON/OFF

HS5_TST

HT.6

Relay 6 W2 Gas Valve 3

ON/OFF

HS6_TST

H.I.R

Heat Interlock Relay

ON/OFF

HIR_TST

HTC.C

Ht.Coil Command Position

0-100

%

HTCLHEAT