APPENDIX D — VFD INFORMATION (cont)

START-UP ASSISTANT MODE — To use the Start-Up

Assistant, perform the following procedure:

1. Select MENU (SOFT KEY 2). The Main menu will be

displayed.

2. Use the UP or DOWN keys to highlight ASSISTANTS

on the display screen and press ENTER (SOFT KEY 2).

3. Use the UP or DOWN keys to highlight Commission

Drive and press SEL (SOFT KEY 2).

4. The Start-Up Assistant will display the parameters that

need to be configured. Select the desired values and press

SAVE (SOFT KEY 2) after every change. The process

will continue until all the parameters are set. The assistant

checks to make sure that entered values are in range.

The assistant is divided into separate tasks. The user can

activate the tasks one after the other or independently. The

tasks are typically done in this order: Application, References

1 and 2, Start/Stop Control, Protections, Constant Speeds, PID

Control, Low Noise Setup, Panel Display, Timed Functions,

and Outputs.
CHANGED PARAMETERS MODE — The Changed Param-

eters mode is used to view and edit recently changed parameters

on the drive. To view the changed parameters, perform the

following procedure:

1. Select MENU (SOFT KEY 2). The Main menu will be

displayed.

2. Use the UP or DOWN keys to highlight CHANGED

PAR on the display screen and press ENTER (SOFT

KEY 2). A list of the recently changed parameters will be

displayed.

3. Use the UP or DOWN keys to highlight the desired pa-

rameter group and press EDIT (SOFT KEY 2) to change

the parameter if desired.

4. Press EXIT (SOFT KEY 1) to exit the Changed Parame-

ters mode.

DRIVE PARAMETER BACKUP MODE — The drive param-

eter back up mode is used to export the parameters from one

drive to another. The parameters can be uploaded from a VFD

to the removable control panel. The control panel can then be

transferred to another drive and the parameters downloaded into

memory.

Depending on the motor and application, there are two

options available. The first option is to download all parame-

ters. This copies both application and motor parameters to the

drive from the control panel. This is recommended when using

the same application for drives of the same size. This can also

be used to create a backup of the parameters group for the

drive.

The second option downloads only the application parame-

ters to the drive. This is recommended when using the same ap-

plication for drives of different sizes. Parameters 9905, 9906,

9907, 9908, 9909, 1605, 1607, 5201, and group 51 parameters

and internal motor parameters are not copied.

Upload All Parameters — To upload and store parameters in

the control panel from the VFD, perform the following

procedure:

1. Select MENU (SOFT KEY 2). The Main menu will be

displayed.

2. Use the UP or DOWN keys to highlight PAR BACKUP

on the display screen and press ENTER (SOFT KEY 2).

3. Use the UP or DOWN keys to highlight UPLOAD TO

PANEL and press SEL (SOFT KEY 2).

4. The text “Copying Parameters” will be displayed with a

progress indicator. To stop the process, select ABORT

(SOFT KEY 1).

5. When the upload is complete, the text “Parameter upload

successful” will be displayed.

6. The display will then return to the PAR BACKUP menu.

Select EXIT (SOFT KEY 1) to return to the main menu.

7. The control panel can now be disconnected from the

drive.

Download All Parameters — To download all parameters

from the control panel to the VFD, perform the following

procedure:

1. Install the control panel with the correct parameters onto

the VFD.

2. Select MENU (SOFT KEY 2). The Main menu will be

displayed.

3. Use the UP or DOWN keys to highlight PAR BACKUP

on the display screen and press ENTER (SOFT KEY 2).

4. Use the UP or DOWN keys to highlight DOWNLOAD

TO DRIVE ALL and press SEL (SOFT KEY 2).

5. The text “Restoring Parameters” will be displayed with a

progress indicator. To stop the process, select ABORT

(SOFT KEY 1).

6. When the download is complete, the text “Parameter

download successful” will be displayed.

7. The display will then return to the PAR BACKUP menu.

Select EXIT (SOFT KEY 1) to return to the main menu.

8. The control panel can now be disconnected from the

drive.

Download Application Parameters — To download applica-

tion parameters only to the control panel from the VFD,

perform the following procedure:

1. Install the control panel with the correct parameters onto

the VFD.

2. Select MENU (SOFT KEY 2). The Main menu will be

displayed.

3. Use the UP or DOWN keys to highlight PAR BACKUP

on the display screen and press ENTER (SOFT KEY 2).

4. Use the UP or DOWN keys to highlight DOWNLOAD

APPLICATION and press SEL (SOFT KEY 2).

5. The text “Downloading Parameters (partial)” will be

displayed with a progress indicator. To stop the process,

select ABORT (SOFT KEY 1).

6. When the download is complete, the text “Parameter

download successful” will be displayed.

7. The display will then return to the PAR BACKUP menu.

Select EXIT (SOFT KEY 1) to return to the main menu.

8. The control panel can now be disconnected from the

drive.

Fig. C — Standard Display Example

Advertising