APPENDIX C — UNIT STAGING TABLES (cont)

STAGING SEQUENCE — SIZE 040 UNITS — 60 Hz

LEGEND

STAGING SEQUENCE — SIZE 040 UNITS — 50 Hz

LEGEND

STAGING SEQUENCE — SIZE 050 UNITS

LEGEND

STAGING SEQUENCE — SIZE 055 UNITS — 60 Hz

LEGEND

CIRCUIT A

STAGE

COMPRESSOR OR UNLOADER

PERCENT

a1

u1

u2

a2

b1

u3

u4

b2

Lead

0

0

0

0

0

0

0

0

0

0%

1

1

1

0

0

0

0

0

0

25%

2

1

0

0

0

0

0

0

0

50%

3

1

0

0

0

1

1

0

0

75%

4

1

0

0

0

1

0

0

0

100%

Lag

0

0

0

0

0

0

0

0

0

0%

1

0

0

0

0

1

1

0

0

25%

2

0

0

0

0

1

0

0

0

50%

3

1

1

0

0

1

0

0

0

75%

4

1

0

0

0

1

0

0

0

100%

0 — Off

a,b — Compressor Circuit Designation

1 — On

u

Unloader

CIRCUIT A

STAGE

COMPRESSOR OR UNLOADER

PERCENT

a1

u1

u2

a2

b1

u3

u4

b2

Lead

0

0

0

0

0

0

0

0

0

0%

1

1

1

1

0

0

0

0

0

19%

2

1

1

0

0

0

0

0

0

37%

3

1

1

1

0

1

1

0

0

41%

4

1

1

0

0

1

1

0

0

59%

5

1

1

1

0

1

0

0

0

62%

6

1

1

0

0

1

0

0

0

80%

7

1

0

0

0

1

1

0

0

89%

8

1

0

0

0

1

0

0

0

100%

Lag

0

0

0

0

0

0

0

0

0

0%

1

0

0

0

0

1

1

0

0

22%

2

0

0

0

0

1

0

0

0

43%

3

1

1

0

0

1

1

0

0

59%

4

1

1

1

0

1

0

0

0

62%

5

1

1

0

0

1

0

0

0

80%

6

1

0

0

0

1

1

0

0

89%

7

1

0

0

0

1

0

0

0

100%

0 — Off

a,b — Compressor Circuit Designation

1 — On

u

Unloader

CIRCUIT A

STAGE

COMPRESSOR OR UNLOADER

PERCENT

a1

u1

u2

a2

b1

u3

u4

b2

Lead

0

0

0

0

0

0

0

0

0

0%

1

1

1

1

0

0

0

0

0

19%

2

1

1

0

0

0

0

0

0

37%

3

1

0

0

0

0

0

0

0

57%

4

1

1

1

0

1

0

0

0

62%

5

1

1

0

0

1

0

0

0

80%

6

1

0

0

0

1

0

0

0

100%

Lag

0

0

0

0

0

0

0

0

0

0%

1

0

0

0

0

1

1

0

0

22%

2

1

1

1

0

1

1

0

0

41%

3

1

1

0

0

1

1

0

0

59%

4

1

1

1

0

1

0

0

0

62%

5

1

1

0

0

1

0

0

0

80%

6

1

0

0

0

1

0

0

0

100%

0 — Off

a,b — Compressor Circuit Designation

1 — On

u

Unloader

CIRCUIT A

STAGE

COMPRESSOR OR UNLOADER

PERCENT

a1

u1

u2

a2

b1

u3

u4

b2

Lead

0

0

0

0

0

0

0

0

0

0%

1

1

1

1

0

0

0

0

0

20%

2

1

1

0

0

0

0

0

0

40%

3

1

0

0

0

0

0

0

0

60%

4

1

0

0

0

1

1

0

0

80%

5

1

0

0

0

1

0

0

0

100%

Lag

0

0

0

0

0

0

0

0

0

0%

1

0

0

0

0

1

1

0

0

20%

2

0

0

0

0

1

0

0

0

40%

3

1

1

1

0

1

0

0

0

60%

4

1

1

0

0

1

0

0

0

80%

5

1

0

0

0

1

0

0

0

100%

0 — Off

a,b — Compressor Circuit Designation

1 — On

u

Unloader