CL-5

CONTROLS SET POINT AND CONFIGURATION LOG (cont)

ITEM

EXPANSION

RANGE

DEFAULT

SETTING

IAQ (cont)
AQ.SP

AIR QUALITY SETPOINTS

AQ.SPIQ.O.P

IAQ Econo Override Pos.

0 - 100%

100

AQ.SPIQ.O.C

IAQ Override Flow

0 - 31000 CFM

10000

AQ.SPDAQ.L

Diff.Air Quality LoLimit

0 - 1000

100

AQ.SPDAQ.H

Diff. Air Quality HiLimit

100 - 2000

700

AQ.SPD.F.OF

DAQ PPM Fan Off Setpoint

0 - 2000

200

AQ.SPD.F.ON

DAQ PPM Fan On Setpoint

0 - 2000

400

AQ.SPIAQ.R

Diff. AQ Responsiveness

-5 - 5

0

AQ.SPOAQ.L

OAQ Lockout Value

0 - 2000

0

AQ.SPOAQ.U

User Determined OAQ

0 - 5000

400

AQ.S.R

AIR QUALITY SENSOR RANGE

AQ.S.RIQ.R.L

IAQ Low Reference

0 - 5000

0

AQ.S.RIQ.R.H

IAQ High Reference

0 - 5000

2000

AQ.S.ROQ.R.L

OAQ Low Reference

0 - 5000

0

AQ.S.ROQ.R.H

OAQ High Reference

0 - 5000

2000

IAQ.P

IAQ PRE-OCCUPIED PURGE

IAQ.PIQ.PG

IAQ Purge

Yes/No

No

IAQ.PIQ.P.T

IAQ Purge Duration

5 - 60 min

15

IAQ.PIQ.P.L

IAQ Purge LoTemp Min Pos

0 - 100%

10

IAQ.PIQ.P.H

IAQ Purge HiTemp Min Pos

0 - 100%

35

IAQ.PIQ.L.O

IAQ Purge OAT Lockout

35 - 70 dF

50

HUMD

HUMIDITY CONFIGURATION

HM.CF

Humidifier Control Cfg.

0 - 4

0

HM.SP

Humidifier Setpoint

0 - 100%

40

H.PID

HUMIDIFIER PID CONFIGS

H.PIDHM.TM

Humidifier PID Run Rate

10 - 120 sec

30

H.PIDHM.P

Humidifier Prop. Gain

0 - 5

1

H.PIDHM.I

Humidifier Integral Gain

0 - 5

0.3

H.PIDHM.D

Humidifier Deriv. Gain

0 - 5

0.3

ACT.C

HUMIDIFIER ACTUATOR CFGS

ACTCSN.1

Humd Serial Number 1

0 - 255

0

ACTCSN.2

Humd Serial Number 2

0 - 255

0

ACTCSN.3

Humd Serial Number 3

0 - 255

0

ACTCSN.4

Humd Serial Number 4

0 - 255

0

ACTCSN.5

Humd Serial Number 5

0 - 255

0

ACTCC.A.LM

Humd Ctrl Angle Lo Limit

0-90

85

DEHU

DEHUMIDIFICATION CONFIG.

D.SEL

Dehumidification Config

0-3(multi-text strings)

0

D.SEN

Dehumidification Sensor

1-3(multi-text strings)

1

D.EC.D

Econ disable in DH mode?

Yes/No

Yes

D.V.CF

Vent Reheat Setpt Select

0-1(multi-text strings)

0

D.V.RA

Vent Reheat RAT offset

0-8 delta F

0

D.V.HT

Vent Reheat Setpoint

55-95 dF

70

D.C.SP

Dehumidify Cool Setpoint

40-55 dF

45

D.RH.S

Dehumidify RH Setpoint

10-90%

55

CCN

CCN CONFIGURATION

CCNA

CCN Address

1 - 239

1

CCNB

CCN Bus Number

0 - 239

0

BAUD

CCN Baud Rate

1 - 5 (multi-text strings)

3

BROD

CCN BROADCST DEFINITIONS

BRODTM.DT

CCN Time/Date Broadcast

ON/OFF

On

BRODOAT.B

CCN OAT Broadcast

ON/OFF

Off

BRODORH.B

CCN OARH Broadcast

ON/OFF

Off

BRODOAQ.B

CCN OAQ Broadcast

ON/OFF

Off

BRODG.S.B

Global Schedule Broadcst

ON/OFF

Off

BRODB.ACK

CCN Broadcast Ack'er

ON/OFF

Off

SC.OV

CCN SCHEDULES-OVERRIDES

SC.OVSCH.N

Schedule Number

0 - 99

1

SC.OVHOL.T

Accept Global Holidays?

YES/NO

No

SC.OVO.T.L.

Override Time Limit

0 - 4 HRS

1

SC.OVOV.EX

Timed Override Hours

0 - 4 HRS

0