Table 62 — Dehumidification Configuration

D.SEL = 1 — The control will perform both dehumidifi-

cation and reheat with modulating valve (hydronic).

D.SEL = 2 — The control will perform dehumidification

and reheat with staged gas only.

D.SEL = 3 — The control will perform both dehumidifi-

cation and reheat with third party heat via an alarm relay.

In the case of D.SEL=3, during dehumidification, the

alarm relay will close to convey the need for reheat. A

typical application might be to energize a 3-way valve to

perform hot gas reheat.

Dehumidification Sensor (D.SEN) — The sensor can be con-

figured for the following settings:
D.SEN = 1 — Initiated by return air relative humidity

sensor.

D.SEN = 2 — Initiated by space relative humidity sensor.

D.SEN = 3 — Initiated by discrete input.
Economizer Disable in Dehum Mode (D.EC.D) — This

configuration determines economizer operation during Dehu-

midification mode.
D.EC.D = YES — Economizer disabled during dehu-

midification (default).

D.EC.D = NO — Economizer not disabled during dehu-

midification.

Vent Reheat Set Point Select (D.V.CF) — This configuration

determines how the vent reheat set point is selected.
D.V.CF = 0 — Reheat follows an offset subtracted from

return air temperature (D.V.RA).

D.V.CF = 1 — Reheat follows a dehumidification heat

set point (D.V.HT).

Vent Reheat RAT Offset (D.V.RA) — Set point offset used

only during the vent mode. The air will be reheated to return-

air temperature less this offset.
Vent Reheat Set Point (D.V.HT) — Set point used only dur-

ing the vent mode. The air will be reheated to this set point.
Dehumidify Cool Set Point (D.C.SP) — This is the dehu-

midification cooling set point.
Dehumidity RH Set Point (D.RH.S) — This is the dehumidi-

fication relative humidity trip point.
OPERATION — Dehumidification and reheat can only occur

if the unit is equipped with either staged gas or hydronic heat.

Dehumidification without reheat can be done on any unit but

Configuration

DEHU

D.SEL must be set to 2.

If the machine’s control type is a TSTAT type (Configura-

tion

UNIT

C.TYP=3 or 4) and the discrete input selection

for the sensor is not configured (D.SEN not equal to 3),

dehumidification will be disabled.

If the machine’s control type is a TSTAT type (Configura-

tion

UNIT

C.TYP=3 or 4) and the economizer is able to

provide cooling, a dehumidification mode may be called out,

but the control will not request mechanical cooling.

If a 2-stage control type is selected (Configuration

UNIT

C.TYP = 4 or 6), then the economizer, if active, locks out

mechanical cooling during the Dehumidification mode.
NOTE: Configuring Configuration

DEHU

D.SEN to 1,2

or 3 will enable the CEM board along with the sensor selected

for control.

NOTE: If Configuration

DEHU

D.SEL = 1 or 2, then

either staged gas or hot water valve control will be automati-

cally enabled (Configuration

HEAT

HT.CF will be set to

either 3 or 4).

If a tempering, unoccupied or “mechanical cooling locked

out” HVAC mode is present, dehumidification will be disabled.

An HVAC: Off, Vent or Cool mode must be in effect to launch

either a Reheat or Dehumidification mode.

If an associated sensor responsible for dehumidification

fails, dehumidification will not be attempted (SPRH, RARH).
Initiating a Reheat or Dehumidification Mode — To call out

a Reheat mode in the Vent or the Off HVAC mode, or to call

out a Dehumidification mode in a Cool HVAC mode, one of

the following conditions must be true:
• The space is occupied and the humidity is greater than

the relative humidity trip point (D.RH.S).

• The space is occupied and the discrete humidity input is

closed.

Dehumidification and Reheat Control — If a dehumidifica-

tion mode is initiated, the rooftop will attempt to lower

humidity as follows:
• Economizer Cooling — The economizer, if allowed to

perform free cooling, will have its control point (Run

Status

VIEW

EC.C.P) set to Configuration

DEHU

D.C.SP. If Configuration

DEHU

D.EC.D is dis-

abled, the economizer will always be disabled during

dehumidification.

• Cooling — For all cooling control types: A High Cool

HVAC mode will be requested internally to the control to

maintain diagnostics, although the end user will see a

Dehumidification mode at the display. In addition, for

multi-stage cooling units the cooling control point will

be set to Configuration

DEHU

D.C.SP (no SASP

reset is applied).

• Reheat When Cooling Demand is Present — For reheat

control during dehumidification: If reheat follows an

offset subtracted from return-air temperature (Configu-

ration

DEHU

D.SEL = 2), then no heating will be

initiated and the alarm relay will be energized. If

Configuration

DEHU

D.SEL = 1 and Configura-

tion

HEAT

HT.CF = staged gas or hot water valve,

then the selected heating control type will operate in the

low heat/modulating mode.

• The heating control point will be whatever the actual

cooling set point would have been (without any supply

air reset applied).

• Reheat During Vent Mode — If configured (Configura-

tion

DEHU

D.V.CF = 0), the heating control point

will be equal to RAT - D.V.RA. If configured (Configu-

ration

DEHU

D.V.CF=1), the heating control point

will be equal to the D.V.HT set point.

Ending Dehumidification and Reheat Control — When ei-

ther the humidity sensor fall 5% below the set point (Configu-

ration

DEHU

D.RH.S) or the discrete input reads

“LOW”, the Dehumidification mode will end.

Temperature Compensated Start —

This logic is

used when the unit is in the unoccupied state. The control will

calculate early Start Bias time based on Space Temperature

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULT

DEHU

DEHUMIDIFICATION CONFIG.

D.SEL

Dehumidification Config

0-3

DHSELECT

0

D.SEN

Dehumidification Sensor

1-3

DHSENSOR

1

D.EC.D

Econ disable in DH mode?

Yes/No

DHECDISA

Yes

D.V.CF

Vent Reheat Setpt Select

0-1

DHVHTCFG

0

D.V.RA

Vent Reheat RAT offset

0-8

deltaF

DHVRAOFF

0

D.V.HT

Vent Reheat Setpoint

55-95

dF

DHVHT_SP

70

D.C.SP

Dehumidify Cool Setpoint

40-55

dF

DHCOOLSP

45

D.RH.S

Dehumidify RH Setpoint

10-90

%

DHRELHSP

55